NCN40-L2-N0-V1 - Inductive sensor | NCN40-L2-N0-V1 - Quad Industry GmbH
Артикул: NCN40-L2-N0-V1
Наименование: Inductive sensor | NCN40-L2-N0-V1
Производитель: Pepperl-Fuchs
|
|
- 40 mm non-flush
- Quick mounting bracket
- Usable up to SIL2 acc. to IEC 61508
Datasheet as PDF in following languages: Technical Data: NCN40-L2-N0-V1General specifications | Switching element function | NAMUR, NC | Rated operating distance | 40 mm | Installation | non-flush | Output polarity | DC | Assured operating distance | 0 ... 32.4 mm | Reduction factor rAl | 0.31 | Reduction factor rCu | 0.3 | Reduction factor r304 | 0.74 | Nominal ratings | Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | Switching frequency | 0 ... 150 Hz | Hysteresis | typ. 5 % | Reverse polarity protection | reverse polarity protected | Short-circuit protection | yes | Current consumption | | | Measuring plate not detected | ≥ 2.2 mA | | Measuring plate detected | ≤ 1 mA | Switching state indication | LED, yellow | Functional safety related parameters | MTTFd | 1670 a | Mission Time (TM) | 20 a | Diagnostic Coverage (DC) | 0 % | Approvals and certificates | UL approval | cULus Listed, General Purpose | CSA approval | cCSAus Listed, General Purpose | CCC approval | CCC approval / marking not required for products rated ≤36 V | Ambient conditions | Ambient temperature | -25 ... 100 В°C (-13 ... 212 В°F) | Storage temperature | -40 ... 100 В°C (-40 ... 212 В°F) | Mechanical specifications | Connection type | Connector M12 x 1 , 4-pin | Housing material | PA | Sensing face | PA | Housing diameter | | Protection degree | IP69K | General information | Use in the hazardous area | see instruction manuals | | Category | 1G; 2G; 3G; 3D |
|