NXS1250C1005/U - 125 HP VFD W/DISPLAY, 575 V, NEMA1 - Quad Industry GmbH

Артикул: NXS1250C1005/U
Наименование: 125 HP VFD W/DISPLAY, 575 V, NEMA1
Производитель: Honeywell


Overview

Variable Frequency Drives (VFD) accept a control input and then output tailored PWM control signal to operate(fans, pumps, etc.) with maximum efficiency. The VFD can be field-programmed without any extra devices or computer connections.

Features

  • Seven configurable applications built in.
  • Easy commissioning through software or control panel.
  • Devices can be wall-mounted or panel-mounted.
  • Eleven protective functions (see Form 63-2600, Users Manual, Technical Data sections).
  • Compact Size.
  • Insulated gate bi-polar transistor (IGBT) technology.
  • Modbus, BacNet, Device Net, Profibus, LobBus, NS available as options cards.

Product Specifications

Dimensions (in.)
18.9 x 45.3 x 14.3
Dimensions (mm)
480 x 1150 x 362
Weight (lb)
321.9 lb
Weight (kg)
146.0 kg
Frequency
0 Hz to 320 Hz
Voltage
575 Vac
Operating Temperature Range (F)
High Overload 14 to 122, Low Overload 14 to 104
Operating Temperature Range (C)
High Overload -10 to 50, Low Overload -10 to 40
Enclosure
NEMA 1
Relay Outputs
24 Vdc/8A, 125 Vdc/0.4A, 250 Vac/8A
Horsepower
125 HP
Current Ratings
125A
Analog Current Output
0 (4) - 20 mA, max 500 ohm
Bypass
Drive alone
Drive Family
NXS
Type of RFI Filter
Industrial filter
Continuous Output Current
overload 1.5 x High overload current (1min/10min), overload 1.1 x Low overload current (1min/10min)
Starting Torque
200% High, 150% Low
Peak Current
2 x high overload current, 2 seconds every 20 seconds
Acceleration time
0 - 3000 sec
Deceleration time
0 - 3000 sec
Analog Voltage Input
0 - 10 Vdc , 200K ohm
Analog Current Input
0 (4) - 20 mA, 250 ohm differential
Digital Output
50 mA/48v open collector
Reference Output Voltage
+10V, +3%, max 10mA
Auxiliary Voltage
24V, ? 15%, max 250 mA
Frame Type
FR9
Layout
Stand-alone drive

 



Назад в раздел