NXBL0250CS313F1110 - 25HP NXS VFD, 3CONT. COOLBLUE BYPASS - Quad Industry GmbH

Артикул: NXBL0250CS313F1110
Наименование: 25HP NXS VFD, 3CONT. COOLBLUE BYPASS
Производитель: Honeywell


Overview

Variable Frequency Drives (VFD) accept a control input and then output tailored PWM control signal to operate (motors, fans, pumps, etc.) with maximum efficiency. The VFD can be field-programmed without any extra devices or computer connections.

Features

  • Seven configurable applications built in.
  • Easy commissioning through software or control panel.
  • Devices can be wall-mounted or panel-mounted.
  • Eleven protective functions (see Form 63-2600, Users Manual, Technical Data sections).
  • Insulated gate bi-polar transistor (IGBT) technology.
  • Modbus, BacNet, Device Net, Profibus, LobBus, NS available as options cards.

Product Specifications

Dimensions (in.)
36H x 12D x 30W
Dimensions (mm)
882H x 294D x 735W
Weight (lb)
124 lb
Weight (kg)
272.8 kg
Frequency
0 Hz to 320 Hz
Voltage
575 Vac
Operating Temperature Range (F)
High Overload 14 to 122, Low Overload 14 to 104
Operating Temperature Range (C)
High Overload -10 to 50, Low Overload -10 to 40
Enclosure
NEMA 3R
Relay Outputs
24 Vdc/8A, 125 Vdc/0.4A, 250 Vac/8A
Horsepower
25 HP
Current Ratings
27A
Analog Current Output
0 (4) - 20 mA, max 500 ohm
Bypass
Drive with 3 contactor bypass
Auto Bypass
Yes
Drive Family
NXS
Contactor
3 Contactors
Disconnect Type
Fused Disconnect
Pilot Lights
Yes
Control Transformer
Yes
Drive Input Disconnect
Yes
Drive Input Fuses
No
Type of RFI Filter
Industrial filter
Continuous Output Current
overload 1.5 x High overload current (1min/10min), overload 1.1 x Low overload current (1min/10min)
Starting Torque
200% High, 150% Low
Peak Current
2 x high overload current, 2 seconds every 20 seconds
Acceleration time
0 - 3000 sec
Deceleration time
0 - 3000 sec
Analog Voltage Input
0 - 10 Vdc , 200K ohm
Analog Current Input
0 (4) - 20 mA, 250 ohm differential
Digital Output
50 mA/48v open collector
Reference Output Voltage
+10V, +3%, max 10mA
Auxiliary Voltage
24V, ? 15%, max 250 mA
Frame Type
FR6
Layout
Vertical

 



Назад в раздел