L6081A1010/U - High and Low limit Aquastat Controller - Quad Industry GmbH

Артикул: L6081A1010/U
Наименование: High and Low limit Aquastat Controller
Производитель: Honeywell


Overview

High limit, low limit and/or circulator controllers used to regulate boiler water temperature in gas- or oil-fired hydronic heating systems.

Features

  • An immersion type liquid-filled sensing element actuates two snap switches.
  • One switch operates as a high limit control.
  • The other switch operates as a low limit and/or circulator control, depending on the model.
  • Controller may be mounted in any positioning and needs no leveling.
  • Separate, easy-to-read, calibrated dial and setpoint adjustments for each switch.
  • Differential adjustment on low limit or circulator switch.
  • All adjustments accessible inside front cover.
  • Push-in terminals for quick connecting.
  • Single sensing element for easy installation.
  • One SPST and one SPDT snap switches act independently at respective temperature settings.

Product Specifications

Hazmat Information
UN1294 Toluene
Application
High and Low limit
Dimensions (in.)
3 7/8 in. high x 4 1/8 in. wide x 2 3/4 in. deep.
Dimensions (mm)
98 mm high x 105 mm wide x 70 mm deep.
Maximum Safe Operating Pressure (psi)
200 psi on immersion well, 100 psi direct immersion.
Maximum Safe Operating Pressure (kPa)
1378 kPa on immersion well, 90 kPa direct immersion.
Temperature Range (F)
-30 F to 150 F at switches, 265 F at sensing element
Temperature Range (C)
-34 C to 66 C at switches, 129 C at sensing element
Includes
3 in. insertion well.
Mounting
Horizontal
Electrical Ratings
0.25 A @ 0.25 to 12 Vdc, At Full Load-- 8A @ 120 Vac: 5.1A @ 240 Vac, At Locked Rotor-- 48A @ 120 Vac: 30.6A @ 240 Vac
Approvals, Underwriters Laboratories Inc.
UL Listed: File No. MP466, Vol. 12, Sec. 4, Guide No. MBPR2
Approvals, Canadian Standards Association
Certified: File No. LR95329-1
Tradeline Value
Tradeline
Electrical Connections
Quick-Connect / Push-in
Operating Humidity Range (% RH)
0 to 95% RH, non-condensing
Operating Temperature Range (F)
High Limit-- 130 F to 240 F, Low Limit-- 110 F to 220 F
Operating Temperature Range (C)
High Limit-- 54 C to 116 C, Low Limit-- 43 C to 104 C
Differential Temperature (F)
10 F Fixed
Well Spud Size (in.)
3/4 in. - 14 NPT
Well Spud Size (mm)
19 mm - 14 NPT
Insulation Depth (in.)
3 in.
Insulation Depth (mm)
76 mm
Electrical Ratings, Ignition
Transformer Load: 360 VA

 



Назад в раздел