General specifications |
Switching element function | DC Dual NC |
Rated operating distance | 3 mm |
Installation | flush mountable |
Output polarity | NAMUR |
Assured operating distance | 0 ... 2.43 mm |
Reduction factor rAl | 0.5 |
Reduction factor r304 | 1 |
Reduction factor rSt37 | 1.2 |
Nominal ratings |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Operating voltage | 5 ... 25 V |
Switching frequency | 0 ... 100 Hz |
Hysteresis | typ. 5 % |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | yes |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
Current consumption | |
| Measuring plate not detected | ≥ 3 mA |
| Measuring plate detected | ≤ 1 mA |
No-load supply current | ≥ 3 mA |
Switching state indication | LED, yellow |
Valve status indication | LED, yellow can be switched off by of DB1 |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
|
| Electromagnetic compatibility | NE 21:2007 |
Ambient conditions |
Ambient temperature | -25 ... 100 В°C (-13 ... 212 В°F) |
Storage temperature | -40 ... 100 В°C (-40 ... 212 В°F) |
Mechanical specifications |
Connection (system side) | Cage tension spring terminals |
Core cross-section (system side) | up to 2.5 mm2 |
Connection (valve side) | Cage tension spring terminals |
Core cross-section (valve side) | up to 2.5 mm2 |
Housing material | PBT |
Sensing face | PBT |
ATEX 1G |
Specific conditions | |
| Lead insertion | The connection cables should either be fixed when laid and mechanically protected or installed in such a way, that a force of 30 N applied in the direction of the cable inlet for one hour, does not lead to any visible displacement of the cable connections, even though the cable sheathing is displaced, see also IEC 60079-11. Depending on the type of installation, a suitable cable in accordance with Type A oder B of IEC 60079-14, must be used. |
ATEX 2G |
Specific conditions | |
| Lead insertion | The connection cables should either be fixed when laid and mechanically protected or installed in such a way, that a force of 30 N applied in the direction of the cable inlet for one hour, does not lead to any visible displacement of the cable connections, even though the cable sheathing is displaced, see also IEC 60079-11. Depending on the type of installation, a suitable cable in accordance with Type A oder B of IEC 60079-14, must be used. |
General information |
Use in the hazardous area | see instruction manual
|
| Category | 1G; 2G; 3G |