| Supply |
| Connection | Power Rail |
| Rated voltage | 20 ... 30 V DC |
| Ripple | < 10 % |
| Power loss | 1.1 W , increase up to 2.2 W in the case of short-circuit between terminals 1 and 3 or 2 and 3 |
| Power consumption | 1.4 W , increase up to 2.2 W in the case of short-circuit between terminals 1 and 3 or 2 and 3 |
| Input |
| Connection | terminals 1, 2, 3 |
| Input signal | 0 ... 20 mA or 4 ... 20 mA |
| Input resistance | approx. 105 Ω , terminals 1, 2 |
| Transmitter supply voltage | > 14.7 V at 20 mA |
| Line fault detection | breakage I ≤ 50 µA , short-circuit I > 25 mA |
| Output |
| Interface | CAN protocol via Power Rail bus |
| Connection | Power Rail |
| Transfer characteristics |
| Deviation | 0.1 % of output signal range at 20 В°C (68 В°F) |
| Electrical isolation |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Directive conformity |
| Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
| Explosion protection | |
| Directive 94/9/EC | EN 60079-0:2006, EN 60079-11: 2007 |
| Standard conformity |
| Insulation coordination | EN 50178:1997 |
| Electrical isolation | EN 60079-11:2007 |
| Electromagnetic compatibility | NE 21:2006 |
| Protection degree | IEC 60529 |
| Climatic conditions | IEC 60721 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
| Damaging gas | acc. to ISA-S71.04-1985, severity level G3 |
| Mechanical specifications |
| Protection degree | IP20 |
| Connection | terminal connection ≤ 2.5 mm2 |
| Mass | approx. 100 g |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) |
| Mounting | DIN rail mounting |
| Data for application in connection with Ex-areas |
| EC-Type Examination Certificate | BAS 99 ATEX 7182 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)GD [EEx ia] IIC |
| Supply | Power Rail |
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) |
| Signal | CAN bus (Power Rail) |
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) |
| Input | terminals 3, 2, 1 and 3, 2 |
| Voltage | 25.4 V |
| Current | 93 mA |
| Output | terminals 2, 1 |
| Voltage | 3.6 V |
| Current | 0 mA |
| Power | 0 mW |
| Statement of conformity | TГњV 00 ATEX 1617 X , observe statement of conformity |
| Group, category, type of protection, temperature class | II 3G EEx nA II T4 |
| Electrical isolation | |
| Input/power supply, internal bus | safe electrical isolation acc. to IEC 60079-11:2007, voltage peak value 375 V |