RSD-GW3-Ex2.DPE - PROFIBUS DP V1-Gateway HART | RSD-GW3-Ex2.DPE - Quad Industry GmbH
Артикул: RSD-GW3-Ex2.DPE
Наименование: PROFIBUS DP V1-Gateway HART | RSD-GW3-Ex2.DPE
Производитель: Pepperl-Fuchs
|
|
- Connects the IS-RPI system with the control system via PROFIBUS DP
- Fieldbus intrinsically safe EEx ib IIC
- Device installation in Zone 1, Zone 2, or Zone 22
- Up to 10 gateways on one intrinsically safe bus network
- PROFIBUS DP V1 up to 1.5 MBit/s
- Up to 8 I/O modules on one gateway via the backplane bus
- PROFIBUS DP media redundancy
- Transfer of HART signals
- LED status indication
- Gateway can be replaced under voltage in zone 1 (hot swap)
- EMC acc. to NAMUR NE 21
Datasheet as PDF in following languages: Technical Data: RSD-GW3-Ex2.DPE| Supply | | Connection | terminals V+, V- | | Rated voltage | 8.88 ... 9.5 V | | Power loss | 8 W | | Power consumption | 8.5 W | | Internal bus | | Connection | backplane bus | | Interface | manufacturer specific bus | | Cycle time | 1.6 ms | | External bus | | Connection | terminals 1+, 2- | | Interface | PROFIBUS with intrinsically safe RS 485 transfer technique | | Transfer rate | 9.6 ... 1500 kBit/s | | Bus address | 1 ... 99 , adjustable via switch | | Terminating impedance | adjustable with sliding switch: I = OFF; ON = ON | | Directive conformity | | Electromagnetic compatibility | | | Directive 2004/108/EC | EN 61326-1:2006 | | Explosion protection | | | Directive 94/9/EC | EN 60079-0:2006, EN 60079-11:2007, EN 61241-0:2006, EN 61241-1:2006 | | Standard conformity | | Insulation coordination | EN 50178 | | Electrical isolation | EN 60079-11:2007 | | Electromagnetic compatibility | NE 21:2006 | | Protection degree | IEC 60529 | | Climatic conditions | IEC 60721 | | Ambient conditions | | Classification | 3K3 | | Ambient temperature | -20 ... 70 В°C (-4 ... 158 В°F) | | Storage temperature | -20 ... 100 В°C (-4 ... 212 В°F) | | Relative humidity | 95 % non-condensing | | Shock resistance | 15 g peak, 11 ms period | | Vibration resistance | 2 g , 10 ... 500 Hz according to IEC 60068-2-6 | | Damaging gas | acc. to ISA-S71.04-1985, severity level G3 | | Mechanical specifications | | Connection type | Terminals | | Core cross-section | max. 2.5 mm2 | | Protection degree | IP20, for on-site installation a separate housing is required with a minimum of IP54 | | Mass | approx. 325 g | | Mounting | DIN rail mounting | | Data for application in connection with Ex-areas | | EC-Type Examination Certificate | DMT 00 ATEX 023 X , for additional certificates see www.pepperl-fuchs.com | | Group, category, type of protection | II 2G EEx ib IIC II (2D) | | Temperature class | T4 | | Supply | only in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34 | | External bus | | | Voltage | ± 3.72 V | | Current | 76.5 mA | | Power | 103 mW | | Voltage | ± 3.75 V | | Internal capacitance | negligible | | Internal inductance | negligible | | External capacitance | 100 µF | | External inductance | 1.5 mH | | L/R-ratio | 344 µH/Ω | | Internal bus | customer specific | | Statement of conformity | | | Group, category, type of protection, temperature class | II 3D IP54 T 90В°C | | Electrical isolation | | | Internal/external bus | no electrical isolation | | Internal bus/power supply | safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V | | External bus/power supply | safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V |
|
Назад в раздел
|