| Supply |
| Connection | terminals 34, 50 V+; 35, 51 V- |
| Rated voltage | 8.88 ... 9.5 V |
| Power loss | 5.2 W |
| Power consumption | 8.5 W |
| Internal bus |
| Connection | backplane bus |
| Interface | manufacturer specific bus |
| Cycle time | 1.6 ms |
| Input |
| Connection | terminals 0+, 1 sig, 2-; 4+, 5 sig, 6-; 8+, 9 sig, 10-; 12+, 13 sig, 14-; 17+, 18 sig, 19-; 21+, 22 sig, 23-; 25+, 26 sig, 27-; 29+, 30 sig, 31- |
| Input signal | 4 ... 22 mA (2-wire) ; 0 ... 22 mA (current source) |
| Input resistance | 22 Ω |
| Transmitter supply voltage | 15.5 V at 20 mA |
| Line fault detection | breakage I ≤ 3.6 mA; short-circuit U ≤ 4 V |
| Transfer characteristics |
| Resolution | 16 Bit |
| Step response | 60 ms (0 ... 90 % of the measured value by smallest filter setting) |
| Deviation | 0.1 % of input signal range at 25 °C (298 K) |
| Directive conformity |
| Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
| Explosion protection | |
| Directive 94/9/EC | EN 60079-0: 2006, EN 60079-11: 2007, EN 60079-26: 2007, EN 61241-0: 2006, EN 61241-11: 2006 |
| Standard conformity |
| Insulation coordination | EN 50178 |
| Electrical isolation | EN 60079-11:2007 |
| Electromagnetic compatibility | NE 21:2006 |
| Protection degree | IEC 60529 |
| Climatic conditions | IEC 60721 |
| Ambient conditions |
| Classification | 3K3 |
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) |
| Storage temperature | -20 ... 100 °C (-4 ... 212 °F) |
| Relative humidity | 95 % non-condensing |
| Shock resistance | 15 g peak, 11 ms period |
| Vibration resistance | 2 g , 10 ... 500 Hz according to IEC 60068-2-6 |
| Damaging gas | acc. to ISA-S71.04-1985, severity level G3 |
| Mechanical specifications |
| Connection type | Terminals |
| Core cross-section | max. 2.5 mm2 |
| Protection degree | IP20, for on-site installation a separate housing is required with a minimum of IP54 |
| Mass | approx. 250 g |
| Mounting | DIN rail mounting |
| Data for application in connection with Ex-areas |
| EC-Type Examination Certificate | DMT 98 ATEX E 017 X , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)2G EEx ia/ib IIB/IIC II (1D)(2D) |
| Temperature class | T4 |
| Supply | only in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34 |
| Input | |
| Voltage | 23.7 V |
| Current | 92.5 mA |
| Power | 548 mW |
| External capacitance | 66 nF |
| External inductance | 2.5 mH |
| Voltage | 28 V |
| Current | 110 mA |
| Internal capacitance | negligible |
| Internal inductance | negligible |
| Internal bus | customer specific |
| Statement of conformity | |
| Group, category, type of protection, temperature class | II 3D IP54 T 90°C |
| Electrical isolation | |
| Input/input | no electrical isolation |
| Input/power supply | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V |
| Input/Internal Bus | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V |
| Internal bus/power supply | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V |