| Product Description |
Input 0/4 mA ... 20 mA 2 x Output 0/4 mA ... 20 mA (current sink) |
| General specifications |
| Signal type | Analog input |
| Supply |
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 20 ... 35 V DC |
| Ripple | within the supply tolerance |
| Power loss | 1.6 W |
| Power consumption | 2.5 W |
| Input |
| Connection | terminals 1+, 2-, 3 or 5-, 6+ |
| Input signal | 0/4 ... 20 mA |
| Voltage drop | ≤ 2.4 V at 20 mA (terminals 5, 6) |
| Input resistance | ≤ 76 Ω terminals 2-, 3 ; ≤ 500 Ω terminals 1+, 3 (250 Ω load) |
| Available voltage | ≥ 16 V at 20 mA terminals 1+, 3 |
| Output |
| Connection | terminals 7+, 8-; 10+, 11- |
| Output signal | 0/4 ... 20 mA (overload > 25 mA) |
| Ripple | max. 50 µA rms |
| External supply (loop) | 11 ... 30 V DC |
| Transfer characteristics |
| Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
| Settling time | 200 µs |
| Directive conformity |
| Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
| Conformity |
| Electromagnetic compatibility | NE 21:2006 |
| Protection degree | IEC 60529:2001 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Mechanical specifications |
| Protection degree | IP20 |
| Mass | approx. 200 g |
| Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with Ex-areas |
| EC-Type Examination Certificate | BAS 99 ATEX 7060 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)GD, [Ex ia] IIC, [Ex iaD] (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] |
| EC-Type Examination Certificate | DMT 01 ATEX E 133 |
| Group, category, type of protection | I (M1) [Ex ia] I |
| Statement of conformity | TUV 99 ATEX 1499 X , observe statement of conformity |
| Group, category, type of protection, temperature class | II 3G Ex nA II T4 [device in zone 2] |
| Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2006, EN 60079-11:2007, EN 61241-11:2006 , EN 60079-15:2005 , EN 50303:2000 |
| International approvals |
| UL approval | |
| Control drawing | 116-0173 (cULus) |
| General information |
| Note | Both output loads must be connected to ensure complete and correct operation within the technical specification. |