| Product Description |
| 24 V DC |
| Supply |
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 20 ... 30 V DC |
| Ripple | ≤ 10 % |
| Rated current | ≤ 50 mA |
| Input |
| Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Output |
| Connection | output I: terminals 7+, 8- ; output II: terminals 10+, 11- |
| Signal level | 1-signal: max. 0.85 V for < 2 mA (short-circuit protected) 0-signal: switched off (off-state current ≤ 10 µA) |
| Output I, II | TTL compatible |
| Collective error message | Power Rail |
| Transfer characteristics |
| Switching frequency | ≤ 5 kHz |
| Directive conformity |
| Electromagnetic compatibility | standards |
| Directive 89/336/EEC | EN 61326, EN 50081-2, NE 21 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Mechanical specifications |
| Protection degree | IP20 |
| Mass | approx. 150 g |
| Data for application in connection with Ex-areas |
| EC-Type Examination Certificate | PTB 00 ATEX 2035 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
| Statement of conformity | TUV 99 ATEX 1499 X , observe statement of conformity |
| Group, category, type of protection, temperature class | II 3G EEx nAC IIC T4 [device in zone 2] |
| Directive conformity | standards |
| Directive 94/9/EC | EN 50014, EN 50020, EN 50021 |