Supply |
Rated voltage | 7.2 V DC , battery operated |
Electrical specifications |
Output rated operating current | 4 ... 20 mA |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V |
Input |
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode |
Current | 4 ... 20 mA |
HART communication | |
| Protocol | HART 7.1, backward compatible |
| Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode |
| Transfer rate | 1200 Bit/s |
| Parameters | primary/secondary master, preambles, retries and short address scan ranges |
Output |
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables |
Transfer characteristics |
Accuracy | current input: 0.125 % of measuring range |
Influence of ambient temperature | current input: 5 µA/K |
Indicators/settings |
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
| Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 |
Conformity |
Protection degree | IEC 60529 |
Ambient conditions |
Ambient temperature | -40 ... 60 В°C (-40 ... 140 В°F) |
Storage temperature | -40 ... 85 В°C (-40 ... 185 В°F) |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
Mechanical specifications |
Protection degree | IP66 |
Material | plastic |
Mass | approx. 750 g |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 in) (without cable glands and antenna) |
Mounting | mounting on field device , panel or pole mounting versions see type code |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate | BVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection, temperature class | II 2 G Ex ia IIC T4 Gb |
Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2007 , EN 60079-31:2009 |
International approvals |
IECEx approval | BVS 11.0061 |