| Fieldbus interface |
| Fieldbus type | FOUNDATION Fieldbus |
| Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) |
| ITK version | 4.51 |
| Implementation | resource block1x RS function block8x AI, 1x MAI transducer block8x sensor TB, 1x concentrator TB |
| Execution time | AI, MAI 40 ms max. |
| Macro cycle | typical for one device 8xAI or 1xMAI max. 500 ms |
| Firmware update | via separate plug connection |
| FDE (Fault Disconnect Equipment) | 6.7 mA |
| Polarity | not polarity sensitive |
| Rated voltage | 9 ... 32 V |
| Rated current | max. 23 mA |
| Indicators/operating means |
| LED PWR | green: on, bus voltage existent |
| LED COM ERR | red: continuous lightning: hardware error; 2 Hz flashing: no bus activities or bus fault; off: no error |
| LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange; off: no error |
| Input |
| Number | 8 |
| Sensor types | see table 1 |
| Grounding | grounding of thermoelements possible |
| Error detection | lead breakage, wiring error, hardware device error |
| Common mode voltage | Input to Input 600 Vpeak |
| Transfer characteristics |
| Deviation | |
| Linearization | T/C input 0.1°C RTD input 0.03°C |
| Internal measurement cycle | for all sensor types max. 1 s |
| Electrical isolation |
| Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V |
| Directive conformity |
| Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
| Standard conformity |
| Electrical isolation | EN 60079-11 |
| Electromagnetic compatibility | NE 21:2006 |
| Protection degree | IEC 60529 |
| Fieldbus standard | IEC 61158-2 |
| Shock resistance | EN 60068-2-27 |
| Vibration resistance | EN 60068-2-6 |
| Ambient conditions |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity | ≤ 95 % non-condensing |
| Shock resistance | 15 g |
| Vibration resistance | 5 g , 10 ... 150 Hz |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
| Mechanical specifications |
| Connection type | plug-in terminals |
| Core cross-section | |
| Bus | up to 2.5 mm2 |
| Inputs | up to 2.5 mm2 |
| Housing material | Polycarbonate |
| Protection degree | IP20 |
| Mass | 360 g |
| Mounting | mounting on DIN rail in cabinet |
| Data for application in connection with Ex-areas |
| EC-Type Examination Certificate | PTB 03 ATEX 2237 |
| Group, category, type of protection, temperature class | II 2(1G/D) G Ex ia IIC T4 , II (1)GD [Ex ia] IIC |
| Bus | FISCO see EC-Type Examination Certificate |
| Inputs | see EC-Type Examination Certificate |
| Statement of conformity | PTB 03 ATEX 2238 X |
| Group, category, type of protection, temperature class | II 3G Ex nA II T4 , II 3G Ex nL IIC T4 , II (3)G [Ex nL] IIC |
| Electrical isolation | |
| Bus | see Statement of Conformity |
| Input | see EC-Type Examination Certificate |
| Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2006 , EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-27:2006 |