Not available for purchase, If you need assistance please contact us sales@quad-industry.com Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com
AS-Interface certificate
Protection degree IP67
Flat or round cable connection (via standardized EEMS base, not included with delivery)
Cable piercing method or terminal compartment flat cable yellow/flat cable black or standard round cable inputs: PG7 screwed connection and cage-clamp terminals
Communication monitoring, turn-off
Power supply of outputs from the external auxiliary voltage
dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply
LED IN
switching state (input); 2 LED yellow
LED OUT
Switching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)
24 V DC ± 15 % PELV
Rated operating voltage
26.5 ... 31.6 V from AS-Interface
Rated operating current
≤ 60 mA (without sensors) / max. 240 mA
Protection class
III
Input
Number/Type
2 inputs for 2- or 3-wire sensors (NPN), DC
Supply
from AS-Interface
Voltage
21 ... 31 V
Current loading capacity
≤ 180 mA (TB ≤ 40 В°C), ≤ 140 mA (TB ≤ 60 В°C), short-circuit protected
Input current
≤ 8 mA (limited internally)
Switching point
0 (unattenuated)
≤ 1.5 mA
1 (attenuated)
≥ 4.5 mA
Output
Number/Type
2 electronic outputs, NPN
Supply
from external auxiliary voltage UAUX
Current
1.5 A per output
Voltage
≥ (UAUX - 0.5 V)
Programming instructions
Profile
S-3.F
IO code
3
ID code
F
Data bits (function via AS-Interface)
inputoutput
D0
IN1-
D1
IN2-
D2
-OUT3
D3
-OUT4
Parameter bits (programmable via AS-i)
function
P0
communication monitoring P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1
not used
P2
not used
P3
not used
Ambient conditions
Ambient temperature
-25 ... 60 В°C (-13 ... 140 В°F)
Storage temperature
-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degree
IP67 according to EN 60529
Connection
cable piercing method or terminal compartment flat cable yellow/flat cable black or standard round cable inputs/outputs: PG7 screwed connection and cage clamp terminals