| Product Description |
Cabinet module 4 inputs (PNP) and 4 electronic outputs |
| General specifications |
| Slave type | Standard slave |
| AS-Interface specification | V2.0 |
| Required master specification | ≥ V2.0 |
| UL File Number | E87056 |
| Indicators/operating means |
| LED PWR/FAULT | dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply |
| LED IN | switching state (input); 4 LED yellow |
| LED OUT | Switching state (output); 4 LED yellow |
| Electrical specifications |
| Auxiliary voltage (output) | 115 / 230 V AC ± 10 % |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current | ≤ 80 mA (without sensors) / max. 230 mA |
| Input |
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
| Supply | from AS-Interface |
| Voltage | 21 ... 31 V DC |
| Current loading capacity | ≤ 150 mA, short-circuit protected |
| Switching point | |
| 0 (unattenuated) | ≤ 2 mA |
| 1 (attenuated) | ≥ 4 mA |
| Output |
| Number/Type | 4 electronic outputs, AC |
| Supply | from external auxiliary voltage UAUX |
| Current | ≤ 2 A total (TB ≤ 50В°C) ≤ 1.5 A total (TB ≤ 60В°C) ≤ 0.7 A total (TB ≤ 70В°C) |
| Voltage | ≥ (UAUX - 2 V) |
| Electrical isolation | AS-Interface/Outputs: Safe isolation according to EN 50178 (250 V AC) |
| Programming instructions |
| Profile | S-7.F |
| IO code | 7 |
| ID code | F |
| Data bits (function via AS-Interface) | input output |
| D0 | IN1 OUT1 |
| D1 | IN2 OUT2 |
| D2 | IN3 OUT3 |
| D3 | IN4 OUT4 |
| Parameter bits (programmable via AS-i) | function |
| P0 | communication monitoring P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| P1 | not used |
| P2 | not used |
| P3 | not used |
| Compliance with standards and directives |
| Standard conformity | |
| Protection degree | EN 60529 |
| Ambient conditions |
| Ambient temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
| Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
| Mechanical specifications |
| Protection degree | IP20 |
| Connection | removable coded terminals, Power Rail |
| Mass | 170 g |
| Mounting | DIN mounting rail |