| Product Description |
G2 flat module 2 inputs (PNP) and 2 electronic outputs |
| General specifications |
| Slave type | Standard slave |
| AS-Interface specification | V2.1 |
| Required master specification | ≥ V2.0 |
| UL File Number | E87056 |
| Indicators/operating means |
| LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor supply |
| LED PWR | AS-Interface voltage; LED green |
| LED AUX | ext. auxiliary voltage UAUX ; LED green |
| LED IN | switching state (input); 2 LED yellow |
| LED OUT | Switching state (output); 2 LED yellow |
| Electrical specifications |
| Auxiliary voltage (output) | 24 V DC ± 15 % PELV |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current | ≤ 40 mA (without sensors) / max. 190 mA |
| Protection class | III |
| Input |
| Number/Type | 2 inputs for 2- or 3-wire sensors (PNP), DC |
| Supply | from AS-Interface |
| Voltage | 21 ... 31 V |
| Current loading capacity | ≤ 150 mA (TB ≤ 40 В°C), ≤ 120 mA (TB ≤ 60 В°C), short-circuit protected |
| Input current | ≤ 8 mA (limited internally) |
| Switching point | |
| 0 (unattenuated) | ≤ 1.5 mA |
| 1 (attenuated) | ≥ 4.5 mA |
| Output |
| Number/Type | 2 electronic outputs, PNP |
| Supply | from external auxiliary voltage UAUX |
| Current | 1.5 A per output 3 A total (TB ≤ 40 В°C), 2 A total (TB ≤ 60 В°C) |
| Voltage | ≥ (UAUX - 0.5 V) |
| Programming instructions |
| Profile | S-3.F |
| IO code | 3 |
| ID code | F |
| Data bits (function via AS-Interface) | input output |
| D0 | IN1 - |
| D1 | IN2 - |
| D2 | - OUT3 |
| D3 | - OUT4 |
| Parameter bits (programmable via AS-i) | function |
| P0 | communication monitoring P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| P1 | not used |
| P2 | not used |
| P3 | not used |
| Compliance with standards and directives |
| Standard conformity | |
| Protection degree | EN 60529 |
| Ambient conditions |
| Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
| Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
| Mechanical specifications |
| Protection degree | IP67 |
| Connection | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
| Mass | 100 g |
| Mounting | Mounting base |