VBG-PN-K30-D-S16 - AS-Interface Gateway/Safety Monitor | VBG-PN-K30-D-S16 - Quad Industry GmbH

Артикул: VBG-PN-K30-D-S16
Наименование: AS-Interface Gateway/Safety Monitor | VBG-PN-K30-D-S16
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • Gateway and safety monitor in one housing
  • Gateway compliant with AS-Interface specification 3.0
  • Connection to PROFINET
  • AS-Interface safety monitor with extended range of functions
  • Safety requirements acc. to category 4, EN 954-1
  • Chip card for storing configuration data
  • 2 safe output relays and 2 safe electronic outputs

Datasheet as PDF in following languages:


Technical Data: VBG-PN-K30-D-S16

Product Description
PROFINET Gateway with integrated safety monitor
General specifications
AS-Interface specificationV3.0
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
Switch-on delay< 10 s
Response delay< 40 ms
UL File NumberE223772
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd200 a
B10d2 E+7
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED ETHERNETPROFINET master detected; LED green
LED AS-i ACTIVEAS-Interface operation normal; LED green
LED CONFIG ERRconfiguration error; LED red
LED PRG ENABLEautom. programming; LED green
LED POWERvoltage ON; LED green
LED PRJ MODEprojecting mode active; LED yellow
LED U AS-iAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED EDM/StartExternal device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuitOutput circuit closed; 4 x green LEDs
Button4
Electrical specifications
Insulation voltage≥ 500 V
Rated operating voltage26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC
Rated operating current≤ 300 mA from AS-Interface
Interface 1
Interface type RJ-45
ProtocolPROFINET according to IEEE 802.3
Transfer rate10 MBit/s / 100 MBit/s , Automatic baud rate detection
Interface 2
Interface type RS 232, serial
Diagnostic Interface
Transfer rate19,2 kBit/s
Interface 3
Interface type Chip card slot
Input
Number/Type4 EDM/Start inputs:
EDM: Inputs for the external device monitoring circuits
Start: start inputs:
Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs)
Output
Safety outputOutput circuits 1 and 2: 2 potential-free contacts,
max. contact load:
3  ADC-13 at 30 VDC,
3 AAC-15 at 30 VAC
Output circuits 3 and 4: 2 PNP transistor outputs
max. contact load:
0.5  ADC-13 at 30  VDC
Connection
PROFINETRJ-45
AS-Interfacespring terminals, removable
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Shock and impact resistanceEN 61131-2:2004
Ambient conditions
Ambient temperature0 ... 55 В°C (32 ... 131 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP20
Material
HousingStainless steel
Mass800 g
Construction typeLow profile housing


Назад в раздел