TRDLS231 - LS range Room thermostat standard with display Thermoplastic (breakproof) high-gloss with white illuminated display screw fixing only, without claws - Quad Industry GmbH

Àðòèêóë: TRDLS231
Íàèìåíîâàíèå: LS range Room thermostat standard with display Thermoplastic (breakproof) high-gloss with white illuminated display screw fixing only, without claws
Ïðîèçâîäèòåëü: JUNG




LS range

Room thermostat standard with display
Thermoplastic (breakproof) high-gloss
with white illuminated display
screw fixing only, without claws

Intended use
*     Measuring and controlling the room temperature
*     Measuring and controlling the floor temperature
*     Room temperature control via floor heating with a limiting function (for example in conjunction with tiled stoves)
*     Can be used for "heating only" or "cooling only"
*     Installable in a box in conformance with DIN 49073
*     Only for use in dry, enclosed rooms


Product characteristics
*     Large display with backlighting
*     Text display for self-explanatory operation
*     Different user languages can be selected
*     Internal temperature sensor
*     An external remote sensor can be connected
*     ECO input [clock] for the activation of a freely settable temperature, e.g. for night reduction
*     Time limit for the manually selected temperature
*     Simply switch between 2 temperatures (comfort, reduction)
*     Short-time timer ("party function")
*     Frost protection function
*     Display of energy consumption for electric heating systems
*     Pulse width modulation (PWM) or two-point control system
*     Adjustable cycle time (PWM), hysteresis and minimum on/off time (two-point)
*     Switch-on delay, such as for burners (with two-point control)
*     Adaptation to valves normally open or closed
*     Valve protection (as a room temperature controller with and without a limiting function)
*     Separate resetting of user and installer settings
*     Heizungsunterbrechung nach Norm EN 50559 einstellbar (nicht f?r Ventile stromlos offen)


The control method depends on the type of heating and is determined by the installer:
Room temperature controller: The heating is turned on when the room temperature falls below the set target temperature (measured with an internal sensor or external remote sensor).
Floor temperature controller: The underfloor heating is turned on when the floor temperature falls below the set target temperature (measured using an external remote sensor).
Room temperature controller with a limiter (in conjunction with underfloor heating): The room temperature is measured and regulated using the internal sensor. An additional external remote sensor is connected to measure the floor temperature, and a target temperature range for the floor is set. The room temperature control is deactivated when the floor temperature is outside of this range. If temperature falls below this range, the heater is turned on, and if the temperature is above this range, the heater is turned off independent of the current room temperature.

Technical data
Rated voltage: AC 230 V ~, 50 Hz, neutral line required
Output: relay (make contact)
Switching current:
as room temperature controller: 10 mA ... 10 (4) A, 230 V ~
as floor temperature controller: 10 mA ... 16 (4) A, 230 V ~
Power consumption: approx. 1.2 W
Ambient temperature: 0 ... +40 °C (no condensation)
Storing temperature: ?20 ... +70 °C (no condensation)
Temperature setting range: in increments of 0.5 °C
as room temperature controller: 5 ... 30 °C
as floor temperature controller: 10 ... 40 °C
Temperature indication: in increments of 0.1 °C
Output signal: pulse width modulation (PWM)
or two-point control (on/off)
PWM cycle time: adjustable (10 ... 30 min)
Hysteresis: adjustable (with two-point control)
Minimum switching time: adjustable (1 ... 30 min)
Power reserve: approx. 10 years (lithium cell)

Material: thermoplastic

Colour: ivory

Manufacturer: JUNG
Ref.-no.: TR D LS 231