Three-way Cartridge Cage Valves are intended for hydronic applications in a normal indoor environment to control flow of hot/chilled water glycol solution up to 60% concentration. These valves are designed for zone control of heating/cooling systems.
Features
Quick open and linear flow characteristics available
Mixing or diverting application
A-AB-B body pattern
7000-series valves for floating and modulating non-fail safe applications
6000-series valves for two-position control
High close-off rating independent of Cv
Available with a variety of North American and international pipe fittings
No tools required for actuator installation or removal
Actuator removal does not require draining system
Service is by replacement of cartridge, not valve body
Cartridge replacement rebuilds valve to factory-new condition
Product Specifications
Maximum Safe Operating Pressure (psi)
300 psi
Maximum Safe Operating Pressure (kPa)
2068 kappa (20 Bar)
Includes
Cartridge changing tool
Used With
VC actuators, On-Off Type
Comments
Quick opening cartridge for use with low or a line voltage SPDT or SPST controller
Approvals, Canadian Standards Association
CSA Certified
Timing
When used with VC series Actuator--On/Off models with 6 seconds, Floating and modulating with 2 min.
Ambient Temperature Range (F)
32 F to 150 F
Ambient Temperature Range (C)
0 C to 65 C
Connection Type
Female NPT
Body Pattern
Three-way A-AB-B
Pipe Size (inch)
1 in.
Pipe Size (DN)
DN25
Fluid Temperature (C)
1 C to 95 C
Fluid Temperature (F)
34 F to 203 F
Maximum Differential Pressure Ratings (Close-off) (psi)
60 psi
Maximum Differential Pressure Ratings (Close-off) (kPa)