| | Similar to image | | BD01-AK1X/S14 TAP-OFF UNIT |
| |
| General technical details: |
| product designation | | tap-off unit for BD01 busbar trunking system |
| Product type designation | | BD01-AK1X/S14 |
| Product function / phase selection | | No |
| Operating current | | |
| | | |
- at 50 Hz / for AC / rated value / maximum
| A | 16 |
- at 60 Hz / for AC / rated value / maximum
| A | 16 |
| Operating frequency | | |
| | Hz | 50… 60 |
| Operating voltage | | |
- at 50 Hz / at AC / rated value / maximum
| V | 400 |
- at 60 Hz / at AC / rated value / maximum
| V | 400 |
| Number of CEE sockets | | 0 |
| Number of safety sockets | | 0 |
| Number of pitch units for width | | 4 |
| Number of other sockets | | 0 |
| |
| Mechanical design: |
| Execution of short-circuit and overloading protection / in the outgoing unit | | 3-pole D01 fuse base |
| Product component / locking | | Yes |
| Product component / outgoing unit for mounting in devices | | No |
| Length | mm | 195 |
| Width | mm | 160 |
| Height | mm | 124 |
| Color | | light grey |
| RAL color number | | RAL 7035 |
| Conductor cross section that can be connected | | |
| | mm? | 0.5… 4 |
| |
| Outgoing unit: |
| Design of the outgoing unit | | cable entry |
| Size of the outgoing feeder | | 1 |
| Number of poles / of the outgoing feeder | | 5 |
| |
| Ambient conditions: |
| Protection class IP | | IP54 |
| |
| Further information: |
| Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/lowvoltage/catalogs |
| Global Industry Mall (Online ordering system) http://www.siemens.com/lowvoltage/mall |
| Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/BVP:034264/all |
| Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=BVP:034264 |
| |
| |
| |
| last change: | Aug 26, 2011 |