General technical details: |
Product designation | tap-off unit for LD busbar trunking system |
Product-type designation | LD-K-1AKE4/GSTZ2 |
Operating current | |
- for circuit 1 / at 50 Hz / for AC / rated value / maximum
| 400 A |
- for circuit 1 / at 60 Hz / for AC / rated value / maximum
| 400 A |
Operating frequency / rated value / minimum | 50 Hz |
Operating frequency / rated value / maximum | 60 Hz |
Operating voltage | |
- at 50 Hz / at AC / rated value / maximum
| 690 V |
- at 60 Hz / at AC / rated value / maximum
| 690 V |
Product function / phase selection | No |
Mechanical design: |
Product component / locking | Yes |
Length | 905 mm |
Width | 565 mm |
Height | 485 mm |
Color | light grey |
Outgoing unit: |
Design of the outgoing unit | cable entry |
Execution of short-circuit and overloading protection / in the outgoing unit | 3-pole NH2 125 A fuse switch-disconnector |
Number of poles / of the outgoing feeder | 4 |
Ambient conditions: |
Protection class IP | IP54 |
Further information: |
Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/lowvoltage/catalogs |
A&D Mall (Online ordering system) http://www.siemens.com/lowvoltage/mall |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/BVP:660804/all |
|
|
|
|
last change: | 09/29/2008 |