| | Similar to image | | SENTRON PAC4200, LCD, 96X96MM POWER MONITORING DEVICE WITH ADAPTER FOR RAIL-MOUNTING MEASUREMENT OF ELECTR. VALUES VAUX: 22-65VDC VIN: MAX.500/289V, 45-65HZ AMPIN: X/1A OR X/5A AC COMPRESSION TYPE TERMINALS |
| |
| General technical data: |
| product designation | | multimeter |
| Product brand name | | SENTRON |
| Product type designation | | PAC4200 |
| Size of multimeter / company-specific | | size 96 |
| Design of the product | | compact |
| Product function | | |
| | | Yes |
| | | Yes |
| | | Yes |
- reactive power measurement
| | Yes |
| | | Yes |
| | | Yes |
| Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | P |
- according to DIN EN 61346-2
| | P |
| |
| Measurement: |
| Measuring methode | | |
| | | TRMS |
| | | TRMS |
| Type of measured value detection | | complete |
| Curve form of the voltage | | sinusoidal or distorted |
| Measurable line frequency | Hz | 45… 65 |
| Operating mode for measured value detection | | |
- automatic line frequency detection
| | Yes |
| | | No |
| | | No |
| |
| Measuring inputs for voltage: |
| Measurable supply voltage | | |
- between (PE)N and L / for AC / maximum nominal value
| V | 289 |
- between the outer conductors / for AC / maximum nominal value
| V | 500 |
- between (PE)N and L / for AC
| V | 11.5… 346 |
- between the outer conductors / for AC
| V | 20… 600 |
| Supply voltage / between the outer conductors / for AC | | |
| | V | 600 |
| Measuring category / for voltage measurement | | CATIII |
| Outer conductors and neutral conductors internal resistance | | |
| | M? | 1.05 |
| Power consumption / for voltage measurement | | |
| | mW | 220 |
| Measuring range extension for voltages | | |
- with external voltage transformers
| | Yes |
| |
| Measuring inputs for current: |
| Measurable current | | |
- 1 / for AC / nominal value
| A | 1 |
- 2 / for AC / nominal value
| A | 5 |
| Relative measurable current / for AC | % | 1… 120 |
| Continuous current / for AC / maximum permissible | A | 10 |
| Apparent power consumption / for current measurement | | |
- with measuring range 1 A / per phase
| mVA | 4 |
- with measuring range 5 A / per phase
| mVA | 115 |
| Short-time current resistance (Icw) / limited to 1 s / rated value | A | 100 |
| Zero-point suppression / for current measurement | | 0 ... 10 % |
| Measuring category / for current measurement | | CATIII |
| Measuring range extension for currents | | |
- with external current transformers
| | Yes |
| |
| Fault limits: |
| Reference condition / for metering precision | | according to IEC61557-12 |
| Formula for relative total measurement inaccuracy | | |
- for measured variable voltage
| | +/- 0.2 % |
- for measured variable current
| | +/- 0.2 % |
- for measured variable output
| | +/- 0.5 % |
- for measured variable output factor
| | +/- 2 % |
- for measured variable THD
| | +/- 2 % |
- for measured variable active energy
| | Class 0.2 according to IEC61557-12 and/or Class 0.2S according to IEC62053-22 |
- for measured variable reactive energy
| | Class 2 according to IEC61557-12 and/or IEC62053-23 |
| |
| Supply voltage: |
| Design of the power supply | | extra-low voltage power supply unit |
| Type of voltage / of supply voltage | | DC |
| Relative symmetrical tolerance / of the supply voltage | % | 10 |
| Measuring category / supply voltage | | CATIII |
| Supply voltage / 1 / for DC | V | 22… 65 |
| Active power consumed | | |
- without expansion module(s) / typical
| W | 5.5 |
- with expansion module(s) / typical
| W | 11 |
| |
| Digital input: |
| Number of digital inputs | | 2 |
| Operating conditions for digital inputs / external voltage supply | | Yes |
| Input voltage / at the digital input | | |
| | V | 24 |
| | V | 30 |
- final value for signal<1>-recognition
| V | 10 |
- initial value for signal<1>-recognition
| V | 19 |
| Input current / at the digital input | | |
| | mA | 4 |
| Initial delay time / at the digital input | | |
- for signal <1> after <0> / maximum
| ms | 5 |
- for signal <0> after <1> / maximum
| ms | 5 |
| |
| Digital output: |
| Number of digital outputs
|