7KM4211-1BB00-3AA0 - SENTRON PAC4200, LCD, 96X96MM POWER MONITORING DEVICE WITH ADAPTER FOR RAIL-MOUNTING MEASUREMENT OF ELECTR. VALUES VAUX: 22-65VDC VIN: MAX.500/289V, 45-65HZ AMPIN: X/1A OR X/5A AC COMPRESSION TYPE TERMINALS (siemens) - Quad Industry GmbH

Артикул: 7KM4211-1BB00-3AA0
Наименование: SENTRON PAC4200, LCD, 96X96MM POWER MONITORING DEVICE WITH ADAPTER FOR RAIL-MOUNTING MEASUREMENT OF ELECTR. VALUES VAUX: 22-65VDC VIN: MAX.500/289V, 45-65HZ AMPIN: X/1A OR X/5A AC COMPRESSION TYPE TERMINALS (siemens)
Производитель: Siemens


Наименование продукта
SENTRON PAC4200, LCD, 96X96MM POWER MONITORING DEVICE WITH ADAPTER FOR RAIL-MOUNTING MEASUREMENT OF ELECTR. VALUES VAUX: 22-65VDC VIN: MAX.500/289V, 45-65HZ AMPIN: X/1A OR X/5A AC COMPRESSION TYPE TERMINALS
Жизненный цикл продукта
7KM4211-1BB00-3AA0">
7KM4211-1BB00-3AA0"> Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
7KM4211-1BB00-3AA0"> 2011-03-09
Similar to image
SENTRON PAC4200, LCD, 96X96MM POWER MONITORING DEVICE WITH ADAPTER FOR RAIL-MOUNTING MEASUREMENT OF ELECTR. VALUES VAUX: 22-65VDC VIN: MAX.500/289V, 45-65HZ AMPIN: X/1A OR X/5A AC COMPRESSION TYPE TERMINALS
 
General technical data:
product designation   multimeter
Product brand name   SENTRON
Product type designation   PAC4200
Size of multimeter / company-specific   size 96
Design of the product   compact
Product function    
  • voltage measurement
  Yes
  • current measurement
  Yes
  • active power measurement
  Yes
  • reactive power measurement
  Yes
  • pulse measurement
  Yes
  • frequency measurement
  Yes
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  P
  • according to DIN EN 61346-2
  P
 
Measurement:
Measuring methode    
  • for voltage measurement
  TRMS
  • for current measurement
  TRMS
Type of measured value detection   complete
Curve form of the voltage   sinusoidal or distorted
Measurable line frequency Hz 45 65
Operating mode for measured value detection    
  • automatic line frequency detection
  Yes
  • set at 50 Hz
  No
  • set to 60 Hz
  No
 
Measuring inputs for voltage:
Measurable supply voltage    
  • between (PE)N and L / for AC / maximum nominal value
V 289
  • between the outer conductors / for AC / maximum nominal value
V 500
  • between (PE)N and L / for AC
V 11.5 346
  • between the outer conductors / for AC
V 20 600
Supply voltage / between the outer conductors / for AC    
  • maximum permissible
V 600
Measuring category / for voltage measurement   CATIII
Outer conductors and neutral conductors internal resistance    
  • for voltage measurement
M? 1.05
Power consumption / for voltage measurement    
  • per phase
mW 220
Measuring range extension for voltages    
  • with external voltage transformers
  Yes
 
Measuring inputs for current:
Measurable current    
  • 1 / for AC / nominal value
A 1
  • 2 / for AC / nominal value
A 5
Relative measurable current / for AC % 1 120
Continuous current / for AC / maximum permissible A 10
Apparent power consumption / for current measurement    
  • with measuring range 1 A / per phase
mVA 4
  • with measuring range 5 A / per phase
mVA 115
Short-time current resistance (Icw) / limited to 1 s / rated value A 100
Zero-point suppression / for current measurement   0 ... 10 %
Measuring category / for current measurement   CATIII
Measuring range extension for currents    
  • with external current transformers
  Yes
 
Fault limits:
Reference condition / for metering precision   according to IEC61557-12
Formula for relative total measurement inaccuracy    
  • for measured variable voltage
  +/- 0.2 %
  • for measured variable current
  +/- 0.2 %
  • for measured variable output
  +/- 0.5 %
  • for measured variable output factor
  +/- 2 %
  • for measured variable THD
  +/- 2 %
  • for measured variable active energy
  Class 0.2 according to IEC61557-12 and/or Class 0.2S according to IEC62053-22
  • for measured variable reactive energy
  Class 2 according to IEC61557-12 and/or IEC62053-23
 
Supply voltage:
Design of the power supply   extra-low voltage power supply unit
Type of voltage / of supply voltage   DC
Relative symmetrical tolerance / of the supply voltage % 10
Measuring category / supply voltage   CATIII
Supply voltage / 1 / for DC V 22 65
Active power consumed    
  • without expansion module(s) / typical
W 5.5
  • with expansion module(s) / typical
W 11
 
Digital input:
Number of digital inputs   2
Operating conditions for digital inputs / external voltage supply   Yes
Input voltage / at the digital input    
  • for DC / rated value
V 24
  • for DC / max.
V 30
  • final value for signal<1>-recognition
V 10
  • initial value for signal<1>-recognition
V 19
Input current / at the digital input    
  • for signal <1>
mA 4
Initial delay time / at the digital input    
  • for signal <1> after <0> / maximum
ms 5
  • for signal <0> after <1> / maximum
ms 5
 
Digital output:
Number of digital outputs

Назад в раздел