| | Similar to image | | SENTRON PAC3200; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES VAUX: 110-340VDC / 95-240VAC VIN: MAX.690/400V; 45-65HZ AMPIN: X/1A OR X/5A AC RING LUG TERMINALS |
| |
| General technical data: |
| product designation | | multimeter |
| product brand name | | SENTRON |
| Product-type designation | | PAC3200 |
| Size of multimeter / company-specific | | size 96 |
| Design of the product | | basic |
| Product function | | |
| | | Yes |
| | | Yes |
| | | Yes |
- reactive power measurement
| | Yes |
| | | Yes |
| | | Yes |
| Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | P |
- according to DIN EN 61346-2
| | P |
| |
| Measurement: |
| Measuring methode | | |
| | | RMS |
| | | TRMS |
| Type of measured value detection | | complete |
| Curve form of the voltage | | sinusoidal or distorted |
| Measurable line frequency | Hz | 45… 65 |
| Operating mode for measured value detection | | |
- automatic line frequency detection
| | Yes |
| | | No |
| | | No |
| |
| Measuring inputs for voltage: |
| Measurable supply voltage | | |
- between (PE)N and L / for AC / maximum nominal value
| V | 400 |
- between the outer conductors / for AC / maximum nominal value
| V | 690 |
- between (PE)N and L / for AC
| V | 40… 480 |
- between the outer conductors / for AC
| V | 70… 831 |
| Supply voltage / between the outer conductors / for AC | | |
| | V | 831 |
| Measuring category / for voltage measurement | | CATIII |
| Outer conductors and neutral conductors internal resistance | | |
| | M? | 1.05 |
| Power consumption / for voltage measurement | | |
| | mW | 220 |
| Measuring range extension for voltages | | |
- with external voltage transformers
| | Yes |
| |
| Measuring inputs for current: |
| Measurable current | | |
- 1 / for AC / nominal value
| A | 1 |
- 2 / for AC / nominal value
| A | 5 |
| Relative measurable current / for AC | % | 1… 120 |
| Continuous current / for AC / maximum permissible | A | 10 |
| Short-time current resistance (Icw) / limited to 1 s / rated value | A | 100 |
| Zero-point suppression / for current measurement | | 0.1 ... 10 % |
| Measuring category / for current measurement | | CATIII |
| Measuring range extension for currents | | |
- with external current transformers
| | Yes |
| |
| Fault limits: |
| Reference condition / for metering precision | | according to IEC62053-22 and IEC62053-23 |
| Formula for relative total measurement inaccuracy | | |
- for measured variable voltage
| | +/- 0.3 % |
- for measured variable current
| | +/- 0.2 % |
- for measured variable output
| | +/- 0.5 % |
- for measured variable output factor
| | +/- 0.5 % |
- for measured variable reactive energy
| | Class 2 according to IEC61557-12 and/or IEC62053-23 |
| |
| Supply voltage: |
| Design of the power supply | | power supply with a wide range of voltages |
| Type of voltage / of supply voltage | | AC/DC |
| Relative symmetrical tolerance / of the supply voltage | % | 10 |
| Measuring category / supply voltage | | CATIII |
| Supply voltage / 1 / at AC | V | 95… 240 |
| Apparent power consumption | | |
- without expansion module(s) / typical
| V·A | 6 |
- with expansion module(s) / maximum
| V·A | 8 |
| Supply voltage / 1 / for DC | V | 110… 340 |
| |
| Digital input: |
| Number of digital inputs | | 1 |
| Input voltage / at the digital input | | |
| | V | 24 |
- final value for signal<1>-recognition
| V | 8 |
- initial value for signal<1>-recognition
| V | 13 |
| Input current / at the digital input | | |
| | mA | 7 |
| Initial delay time / at the digital input | | |
- for signal <1> after <0> / maximum
| ms | 5 |
- for signal <0> after <1> / maximum
| ms | 5 |
| |
| Digital output: |
| Number of digital outputs | | 1 |
| Design of digital outputs | | switching or pulse output function |
| Norm / for impulse equipment | | according to IEC62053-31 |
| Pulse duration | ms | 30… 500 |
| Adjustable time period / minimum | ms | 10 |
Operating voltage / as ou
|