| | SIMATIC NET, CP 343-1 ADVANCED COMMUNICATION PROCESSOR FOR CONNECTING SIMATIC S7-300 TO IND. ETHERNET VIA PROFINET-IO CONTROLLER, PROFINET CBA,ISO, TCP/IP AND UDP, S7-KOMM., FETCH/WRITE, SEND/RECEIVE, WITH AND W/O RFC1006, HTTP W JAVA, MULTICAST, LOAD. COMM. BLOCKS, HTML DIAGN.,FTP CLIENT/SERVER E-MAIL, SNMP, DHCP, NTP-CPU SYNC, 10/100 MBIT, ONLY RJ45 PORT |
| Transmission rate | |
| Transfer rate | |
| | 10… 100 Mbit/s |
| Interfaces | |
| Number of electrical connections | |
- at interface 1 / in accordance with Industrial Ethernet
| 1 |
| | 1 |
| design of the removable storage / C-PLUG | Yes |
| Supply voltage, current consumption, power loss | |
| Type of voltage / of supply voltage | DC |
| Supply voltage | |
| | 5 V |
| | 24 V |
| Relative positive tolerance / at 24 V / with DC | 20 % |
| Relative negative tolerance / at 24 V / with DC | 15 % |
| Consumed current | |
- from backplane bus / at 5 V / for DC / [nicht versorgt - typisch]
| 0.14 A |
| Resistive loss | 14.7 W |
| Permitted ambient conditions | |
| Ambient temperature | |
| | 0… 60 °C |
| | -40… +70 °C |
| | -40… +70 °C |
| Relative humidity | |
- at 25 °C / without condensation / during operating / maximum
| 95 % |
| Protection class IP | IP20 |
| Design, dimensions and weight | |
| Width | 80 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Net weight | 0.8 kg |
| Performance data / open communication | |
| Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum | 16 |
| Data volume | |
- as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum
| 8 Kibyte |
- as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
| 8 Kibyte |
- as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
| 8 Kibyte |
- as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum
| 2 Kibyte |
| Number of Multicast stations | 16 |
| Performance data / S7 communication | |
| Number of possible connections / [nicht versorgt - f?r S7-Kommunikation] | |
- [nicht versorgt - maximal]
| 16 |
| Performance data / multi-protocol mode | |
| Number of active connections / [nicht versorgt - bei Multiprotokollbetrieb] | 48 |
| Performance data / IT functions | |
| Number of possible connections | |
- [nicht versorgt - als Client] / [nicht versorgt - mittels FTP] / [nicht versorgt - maximal]
| 10 |
- [nicht versorgt - als Server]
| |
- [nicht versorgt - mittels FTP] / [nicht versorgt - maximal]
| 2 |
- [nicht versorgt - mittels HTTP] / [nicht versorgt - maximal]
| 4 |
- as e-mail client / maximum
| 1 |
| Amount of data / [nicht versorgt - als Nutzdaten f?r E-Mail] / [nicht versorgt - maximal] | 8 Kibyte |
| Storage capacity / of user memory | |
- as flash memory file system
| 28 Mibyte |
- [nicht versorgt - als RAM]
| 30 Mibyte |
| Number of possible write cycles / flash memory cells | 100000 |
| Performance data / PROFINET communication / as PN IO-Controller | |
| Number of PN IO-Devices / on PROFINET IO-Controller / usable / total | 125 |
| Number of external PN IO lines / with PROFINET / per rack | 1 |
| Amount of data | |
- [nicht versorgt - als Nutzdaten f?r Eingangsvariablen] / [nicht versorgt - als PROFINET IO-Controller] / [nicht versorgt - maximal]
| 4 Kibyte |
- [nicht versorgt - als Nutzdaten f?r Eingangsvariablen] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
| 4 Kibyte |
- [nicht versorgt - als Nutzdaten f?r Eingangsvariablen je PN IO-Device] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
| 240 byte |
- [nicht versorgt - als Nutzdaten f?r Ausgangsvariablen je PN IO-Device] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
| 240 byte |
| Performance data / PROFINET CBA | |
| Number of remote connection partners / with PROFINET CBA | 64 |
| Number of connections / with PROFINET CBA / total | 1000 |
| Amount of data | |
- [nicht versorgt - als Nutzdaten f?r digitale Eing?nge] / [nicht versorgt - bei PROFINET CBA] / [nicht versorgt - maximal]
| 8 Kibyte |
- [nicht versorgt - als Nutzdaten f?r digitale Ausg?nge] / [nicht versorgt - bei PROFINET CBA] / [nicht versorgt - maximal]
| 8 Kibyte |
- [nicht versorgt - als Nutzdaten f?r Arrays und Datentypen]
| |
- [nicht versorgt - bei azyklischer ?bertragung] / [nicht versorgt - bei PROFINET CBA] / [nicht versorgt - maximal]
| 8 Kibyte |
- [nicht versorgt - bei zyklischer ?bertragung] / [nicht versorgt - bei PROFINET CBA] / [nicht versorgt - maximal]
| 450 byte |
- [nicht versorgt - bei lokaler Verschaltung] / [nicht versorgt - bei PROFINET CBA] / [nicht versorgt - maximal]
| 2400 byte |
| Performance data / PROFINET CBA / remote connection / with acyclic transmission | |
| Updating time / [nicht versorgt - der remote-Verschaltungen] / [nicht versorgt - bei azyklischer ?bertragung] / [nicht versorgt - bei PROFINET CBA] | 100 ms |
Number of remote connections to input variables / with acyclic transmission / with PRO
|