| | |
| |
| General technical data: |
| Product brand name | | SIPLUS ECC8000 |
| Product component / load outputs | | Yes |
| Number of load outputs | | 1 |
| Number of interfaces / to IEC 61851 | | 1 |
| charging current | A | 13/ 32 |
| Product description | | Prefabricated function unit for installation in simple charging column |
| Product function / power measurement | | Yes |
| Number of power measuring points | | 1 |
| Degree of pollution | | 2 (requirement on cabinet) |
| Protection class IP | | IP00 |
| Overvoltage class | | 2 |
| FI type | | Type A |
| Installation altitude / at a height over sea level / maximum | m | 1,000 |
| Ambient temperature / during storage | °C | -20… 60 |
| Ambient temperature / during operating | °C | -5… 45 |
| Ambient temperature / during transport | °C | -20… 60 |
| Relative humidity / during operating phase / maximum | % | 95 |
| Product component / Heating | | Yes |
| Product function / Overvoltage protection | | No |
| |
| Inputs: | | |
| Type of voltage / of supply voltage | | AC |
| Operating voltage / for AC / rated value | V | 400 |
| Input voltage | V | 360… 440 |
| Line frequency / 1 / nominal value | Hz | 50 |
| Insulation voltage / rated value | V | 440 |
| Suitable for operation / for line system | | TNS |
| Current / for AC / rated value | A | 35 |
| |
| Outputs: | | |
| Phase number / of the outputs | | 3 |
| |
| Communication: |
| Product function / bus-communication | | No |
| protocol / is supported | | |
- communication to electric vehicle according to IEC 61851
| | Yes |
| | | No |
| |
| Electromagnetic compatibility: | | |
| Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV / 5 kHz AC supply cables and functional ground, 1 kV / 5 kHz control cables and input/output signals |
| Conductor-bound parasitic coupling SURGE / according to IEC 61000-4-5 | | Asymmetrical: supply lines 2 kV, signal lines >30 m 1 kV, evaluation criterion B. Symmetrical: supply lines 1 kV, evaluation criterion B |
| Electrostatic discharge / according to IEC 61000-4-2 | | 4 kV contact discharge / 8 kV air discharge, evaluation criterion B |
| Conducted interference as high-frequency radiation / according to IEC 61000-4-6 | | 3 V effective in frequency range 0.15 to 80.0 MHz, evaluation criterion A |
| Magnetic field immunity at power frequencies / to EN 61000-4-8 | | 100 A/m at 50 Hz and 60 Hz, evaluation criterion A |
| EMC emitted interference / according to IEC 61000-6-3 | | Suitable for operation in residential, public and industrial environments |
| |
| Mechanical features: | | |
| Resistance against shock | | |
- according to IEC 60068-2-27
| | 15g / 11 ms / 3 shocks / axis |
- during transport / to IEC 60068-2-29
| | 1000 shocks / axis, 25g, 6 ms |
| Vibration resistance | | |
- during transport / to IEC 60068-2-6
| | 5 ... 500 Hz / 1g / 10 cycles |
- during operating phase / to IEC 60068-2-6
| | 5 ... 150 Hz / 1g / 10 cycles |
| |
| Installation/mounting/dimensions: |
| Built in orientation | | vertical |
| Type of mounting | | screw fixing |
| Width | mm | 240 |
| Height | mm | 900 |
| Depth | mm | 200 |
| Net weight | kg | 12 |
| |
| Certificates/approvals: | | |
| |
| |
| Further information: |
| Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs |
| Industry Mall (Online ordering system) http://www.siemens.com/industrial-controls/mall |
| Cax online generator: http://www.siemens.com/cax |
| Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/6FE1086-0SY00-1AA0/all |
| Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=6FE1086-0SY00-1AA0 |
| |
| |
| | |
| |
| last change: | Aug 25, 2011 |