| | SIMATIC S7-400H, CPU 412-3H CENTRAL UNIT FOR S7-400H AND S7-400F/FH, 3 INTERFACES: 1 MPI/DP AND 2 FOR SYNC MODULES 768 KB MEMORY (256 KB DATA/512 KB CODE) |
| |
| General information |
| Hardware product version | 1 |
| Firmware version | V4.5 |
| Engineering with |
| Programming package | STEP7 V 5.3 SP2 or higher with HW update |
| CiR - Configuration in RUN |
| CiR synchronization time, basic load | 150 ms |
| CiR synchronization time, time per I/O slave | 40 µs |
| Supply voltage |
| 24 V DC | No; Power supply via system power supply |
| Input current |
| from backplane bus 5 V DC, typ. | 1.2 A |
| from backplane bus 5 V DC, max. | 1.5 A |
| from backplane bus 24 V DC, max. | 150 mA; Per DP interface |
| from interface 5 V DC, max. | 90 mA; At each DP interface |
| Power losses |
| Power loss, typ. | 5.5 W |
| Backup battery |
| Battery operation | |
| Backup current, typ. | 190 µA; Valid up to 40°C |
| Backup current, max. | 660 µA |
| Backup time, max. | Dealt with in the module data manual with the secondary conditions and the factors of influence |
| Feeding of external backup voltage to CPU | 5 to 15 VDC |
| Feeding of external backup voltage to CPU | 5 to 15 VDC |
| Memory |
| Work memory |
| integrated | 768 kbyte |
| integrated (for program) | 512 kbyte |
| integrated (for data) | 256 kbyte |
| expandable | No |
| Load memory |
| expandable FEPROM | Yes |
| expandable FEPROM, max. | 64 Mbyte |
| integrated RAM, max. | 256 kbyte |
| expandable RAM | Yes |
| expandable RAM, max. | 64 Mbyte |
| Backup |
| present | Yes |
| with battery | Yes; all data |
| without battery | No |
| CPU processing times |
| for bit operations, min. | 0.075 µs |
| for word operations, min. | 0.075 µs |
| for fixed point arithmetic, min. | 0.075 µs |
| for floating point arithmetic, min. | 0.225 µs |
| CPU-blocks |
| DB |
| Number, max. | 4095; Number range: 1 to 4095 |
| Size, max. | 64 kbyte |
| FB |
| Number, max. | 2048; Number range: 0 to 2047 |
| Size, max. | 64 kbyte |
| FC |
| Number, max. | 2048; Number range: 0 to 2047 |
| Size, max. | 64 kbyte |
| OB |
| Size, max. | 64 kbyte |
| Number of time alarm OBs | 4 |
| Number of delay alarm OBs | 4 |
| Number of time interrupt OBs | 4 |
| Number of process alarm OBs | 4 |
| Nesting depth |
| per priority class | 24 |
| additional within an error OB | 1 |
| Counters, timers and their retentivity |
| S7 counter |
| Number | 2048 |
| Retentivity |
| adjustable | Yes |
| lower limit | 0 |
| upper limit | 2047 |
| preset | Z 0 to Z 7 |
| Counting range |
| lower limit | 0 |
| upper limit | 999 |
| IEC counter |
| present | Yes |
| Type | SFB |
| S7 times |
| Number | 2048 |
| Retentivity |
| adjustable | Yes |
| lower limit | 0 |
| upper limit | 2047 |
| preset | No times retentive |
| Time range |
| lower limit | 10 ms |
| upper limit | 9990 s |
| IEC timer |
| present | Yes |
| Type | SFB |
| Data areas and their retentivity |
| retentive data area, total | Total working and load memory (with backup battery) |
| Flag |
| Number, max. | 8 kbyte |
| Retentivity available | Yes |
| Retentivity preset | MB 0 to MB 15 |
| Number of clock memories | 8; (in 1 memory byte) |
| Data blocks |
| Number, max. | 4095; Number range: 1 to 4095 |
| Size, max. | 64 kbyte |
| Local data |
| adjustable, max. | 16 kbyte |
| preset | 8 kbyte |
| Address area |
| I/O address area |
| Inputs | 8 kbyte |
| Outputs | 8 kbyte |
| of which, distributed |
| MPI/DP interface, inputs | 2 kbyte |
| MPI/DP interface, outputs | 2 kbyte |
| Process image |
| Inputs, adjustable | 8 kbyte |
| Outputs, adjustable | 8 kbyte |
| Inputs, default | 256 byte |
| Outputs, default | 256 byte |
| consistent data, max. | 244 byte |
| Access to consistent data in process image | Yes |
| Subprocess images |
| Number of subprocess images, max. | 15 |
| Digital channels |
| Inputs | 65536 |
| Outputs |
|