| | SIMATIC DP, INTERFACE MODULE IM151-1 FO FOR ET200S; TRANSMISS. RATE UP TO 12MBIT/S; DATA VOLUME 128 BYTE FOR EACH INPUT AND OUTPUT; MAX. OF 63 POWER, ELECTR. OR MOTOR STARTER MODULES CONNECTABLE; BUS INTERFACING VIA INTEGR. FO INTERFACE INCL. TERMINATING MODULE |
| |
| General information |
| Vendor identification (VendorID) | 806Bh |
| Supply voltage |
| Mains buffering |
| Mains buffering, min. | 20 ms |
| Input current |
| from supply voltage 1L+, max. | 200 mA |
| Output current |
| Current output to backplane bus (DC 5 V), max. | 700 mA |
| Power losses |
| Power loss, typ. | 3.3 W |
| Address area |
| Addressing volume |
| Outputs | 128 byte |
| Inputs | 128 byte |
| Interfaces |
| Interface physics, FOC | Yes; 4 x Simplex socket |
| PROFIBUS DP |
| Cable length, max. | 2 m |
| Transmission rate, max. | 12 Mbit/s; 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 12 Mbit/s |
| SYNC capability | Yes |
| FREECE capability | Yes |
| Direct data exchange (slave-to-slave communication) | Yes |
| Protocols |
| Further protocols |
| PROFIBUS DP protocol | Yes |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) | No |
| Interrupts/diagnostics/status information |
| Alarms |
| Alarms | No |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostics indication LED |
| Bus fault BF (red) | Yes |
| Group error SF (red) | Yes |
| Monitoring 24 V voltage supply ON (green) | Yes |
| Galvanic isolation |
| between backplane bus and electronics | No |
| between supply voltage and electronics | No |
| Permissible potential difference |
| between different circuits | 500 V DC |
| Isolation |
| Isolation checked with | 57 V DC / 60 V AC |
| Dimensions |
| Width | 45 mm |
| Height | 119.5 mm |
| Depth | 75 mm |
| Weight |
| Weight, approx. | 150 g |
| Status | Mar 12, 2012 |