| | SIMATIC DP, HART ANALOG OUTPUT SM 332, 8AO, 0/4 - 20MA HART, FOR ET200M WITH IM153-2, 20 PIN |
| |
| Supply voltage |
| Load voltage L+ |
| Rated value (DC) | 24 V |
| Input current |
| from load voltage L+ (without load), max. | 350 mA |
| from backplane bus 5 V DC, max. | 100 mA |
| Power losses |
| Power loss, typ. | 6 W |
| Analog outputs |
| Number of analog outputs | 8 |
| Current output, no-load voltage, max. | 24 V |
| Output ranges, current |
| 0 to 20 mA | Yes |
| -20 to +20 mA | No |
| 4 to 20 mA | Yes |
| Load impedance (in rated range of output) |
| with current outputs, max. | 750 Ω |
| with current outputs, inductive load, max. | 10 mH |
| Cable length |
| Cable length, shielded, max. | 800 m |
| Analog value creation |
| Integrations and conversion time/ resolution per channel |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Settling time |
| for resistive load | 0.1 ms |
| for inductive load | 0.5 ms |
| Errors/accuracies |
| Operational limit in overall temperature range |
| Current, relative to output area | +/- 0,2 % |
| Basic error limit (operational limit at 25 °C) |
| Current, relative to output area | +/- 0,1 % |
| Interrupts/diagnostics/status information |
| Substitute values connectable | Yes |
| Alarms |
| Diagnostic alarm | Yes |
| Diagnostic messages |
| Diagnostic information readable | Yes |
| Galvanic isolation |
| Galvanic isolation analog outputs |
| between the channels and the backplane bus | Yes |
| Isolation |
| Isolation checked with | 500 V DC |
| Connection method |
| required front connector | 20-pin |
| Dimensions |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weight |
| Weight, approx. | 220 g |