6ES7314-6BH04-0AB0 - SIMATIC S7-300, CPU 314C-2 PTP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED INTERFACE RS485, INTEGRATED 24V DC POWER SUPPLY, 192 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED (siemens) - Quad Industry GmbH

Артикул: 6ES7314-6BH04-0AB0
Наименование: SIMATIC S7-300, CPU 314C-2 PTP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED INTERFACE RS485, INTEGRATED 24V DC POWER SUPPLY, 192 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC S7-300, CPU 314C-2 PTP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED INTERFACE RS485, INTEGRATED 24V DC POWER SUPPLY, 192 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2011-05-20
SIMATIC S7-300, CPU 314C-2 PTP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED INTERFACE RS485, INTEGRATED 24V DC POWER SUPPLY, 192 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED
General information
Hardware product version 01
Firmware version V3.3
Engineering with
Programming package STEP7 as of V5.5 + SP1 or STEP 7 V5.3 + SP2 or higher with HSP 204
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
External protection for supply cables (recommendation) Miniature circuit breaker, type C; min 2 A; miniature circuit breaker type B, min. 4 A
Mains buffering
Mains/voltage failure stored energy time 5 ms
Repeat rate, min. 1 s
Digital inputs
Load voltage L+
Rated value (DC) 24 V
Reverse polarity protection Yes
Digital outputs
Load voltage L+
Rated value (DC) 24 V
Reverse polarity protection No
Input current
Current consumption (rated value) 660 mA
Current consumption (in no-load operation), typ. 150 mA
Inrush current, typ. 5 A
I²t 0.7 A²·s
Digital inputs
from load voltage L+ (without load), max. 80 mA
Digital outputs
from load voltage L+, max. 50 mA
Power losses
Power loss, typ. 13 W
Memory
Work memory
integrated 192 kbyte
expandable No
Size of retentive memory for retentive data blocks 64 kbyte
Load memory
pluggable (MMC) Yes
pluggable (MMC), max. 8 Mbyte
Data management on MMC (after last programming), min. 10 a
Backup
present Yes; Guaranteed by MMC (maintenance-free)
without battery Yes; Program and data
CPU processing times
for bit operations, min. 0.06 µs
for word operations, min. 0.12 µs
for fixed point arithmetic, min. 0.16 µs
for floating point arithmetic, min. 0.59 µs
CPU-blocks
Number of blocks (total) 1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max. 1024; Number range: 1 to 16000
Size, max. 64 kbyte
FB
Number, max. 1024; Number range: 0 to 7999
Size, max. 64 kbyte
FC
Number, max. 1024; Number range: 0 to 7999
Size, max. 64 kbyte
OB
Description see instruction list
Size, max. 64 kbyte
Number of free cycle OBs 1; OB 1
Number of time alarm OBs 1; OB 10
Number of delay alarm OBs 2; OB 20, 21
Number of time interrupt OBs 4; OB 32, 33, 34, 35
Number of process alarm OBs 1; OB 40
Number of startup OBs 1; OB 100
Number of asynchronous error OBs 4; OB 80, 82, 85, 87
Number of synchronous error OBs 2; OB 121, 122
Nesting depth
per priority class 16
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 256
Retentivity
adjustable Yes
lower limit 0
upper limit 255
preset Z 0 to Z 7
Counting range
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
S7 times
Number 256
Retentivity
adjustable Yes
lower limit 0
upper limit 255
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, max. 64 KB
Flag
Number, max. 256 byte
Retentivity available Yes; MB 0 to MB 255
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Data blocks
Number, max. 1024; Number range: 1 to 16000
Size, max. 64 kbyte
Retentivity adjustable Yes; via non-retain property on DB
Retentivity preset Yes
Local data
per priority class, max. 32 kbyte; Max. 2048 bytes per block

Назад в раздел