| SIMATIC DP, ET 200M INTERFACE IM 153-4 PN IO HIGH FEATURE FOR MAX. 12 S7-300 MODULES, SUPPORTS FAIL SAFE MODULES, HART MODULES SHARED DEVICE, MEDIUM REDUNDANCY PROTOCOL |
|
General information |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 0302H |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
permissible range (ripple included), lower limit (DC) | 18.5 V |
permissible range (ripple included), upper limit (DC) | 30.2 V |
External protection for supply cables (recommendation) | In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A) |
Mains buffering |
Mains/voltage failure stored energy time | 5 ms |
Input current |
Current consumption, max. | 600 mA |
Inrush current, typ. | 4 A |
I²t | 0.09 A²·s |
Output voltage |
Rated value, 5 V DC | Yes |
Output current |
for backplane bus (5 V DC), max. | 1.5 A |
Power losses |
Power loss, typ. | 6 W; Typical |
Address area |
Addressing volume |
Outputs | 192 byte |
Inputs | 672 byte; Extended HART user data |
Hardware configuration |
Number of modules per DP slave interface, max. | 12 |
Communication functions |
Bus protocol/transmission protocol | PN IO |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Connection to network LINK (green) | Yes |
Transmit/receive RX/TX (yellow) | Yes |
Isolation |
Isolation checked with | Between Profinet and 24 V supply: 1500 V AC Between functional grounding and 24 V supply: 500 V DC |
Ambient conditions |
Operating temperature |
Min. | 0 °C |
max. | 60 °C |
Air pressure |
Operating altitude above sea level, max. | 2000 m |
Degree and class of protection |
IP20 | Yes |
Dimensions |
Width | 40 mm |
Height | 125 mm |
Depth | 118 mm |
Weight |
Weight, approx. | 215 g |
Status | Mar 12, 2012 |