| | SIMATIC DP, ET 200M INTERFACE FOR MAX. 8 S7-300 MODULES, WITH REDUNDANCY, TIME STAMPING |
| |
| General information |
| Vendor identification (VendorID) | 801Eh |
| Supply voltage |
| 24 V DC | Yes |
| permissible range (ripple included), lower limit (DC) | 20.4 V |
| permissible range (ripple included), upper limit (DC) | 28.8 V |
| External protection for supply cables (recommendation) | not necessary |
| Mains buffering |
| Mains/voltage failure stored energy time | 5 ms |
| Input current |
| Current consumption, max. | 550 mA; at 24 V DC |
| Inrush current, typ. | 2.5 A |
| I²t | 0.1 A²·s |
| Output voltage |
| Rated value, 5 V DC | Yes |
| Output current |
| for backplane bus (5 V DC), max. | 1 A |
| Power losses |
| Power loss, typ. | 5 W |
| Address area |
| Addressing volume |
| Outputs | 128 byte |
| Inputs | 128 byte |
| Hardware configuration |
| Number of modules per DP slave interface, max. | 8 |
| Time stamping |
| Accuracy | 10 ms; 10 ms / 3 ms |
| Number of message buffers | 15 |
| Messages per message buffer | 20 |
| Number of stampable digital inputs, max. | 128 |
| Time format | RFC 1119 Internet (ISP) |
| Time resolution | 1 ms |
| Time interval for transmitting the message buffer if a message is present | 1000 ms |
| Time stamp on signal change | rising / falling edge as signal entering or exiting |
| Interfaces |
| Interface physics, RS 485 | Yes |
| PROFIBUS DP |
| Node addresses | 1 to 125 permitted |
| Automatic detection of transmission speed | Yes |
| PROFIBUS DP, output current, max. | 90 mA |
| Transmission rate, max. | 12 Mbit/s |
| SYNC capability | Yes |
| FREECE capability | Yes |
| Direct data exchange (slave-to-slave communication) | Yes; Sender |
| PROFIBUS DP | 9-pin sub D socket |
| 1st interface |
| DP slave |
| GSD file | (for DPV1) SIEM801E.GSD; SI01801E.GSG (for IM 153-2AA0x); SI02801E.GSG (for IM 153-2BA0x) |
| Automatic baud rate search | Yes |
| Communication functions |
| Bus protocol/transmission protocol | PROFIBUS DP to EN 50170 |
| Isolation |
| Isolation checked with | Isolation voltage 500 V |
| Ambient conditions |
| Operating temperature |
| Min. | 0 °C |
| max. | 60 °C |
| Degree and class of protection |
| IP20 | Yes |
| Dimensions |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weight |
| Weight, approx. | 360 g |
| Status | Mar 12, 2012 |