| | SIMATIC DP, ET 200ECO PN, 4 AO U/I; 4 X M12, DEGREE OF PROTECTION IP67 |
| |
| General information |
| Vendor identification (VendorID) | 002AH |
| Device identifier (DeviceID) | 0306H |
| Supply voltage |
| 24 V DC | Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current |
| Current consumption, typ. | 280 mA |
| Encoder supply |
| Number of outputs | 4 |
| 24 V encoder supply |
| Short-circuit protection | Yes; Electronic at 1.4 A |
| Output current, max. | 1 A |
| Power losses |
| Power loss, typ. | 5.5 W |
| Analog outputs |
| Number of analog outputs | 4 |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 30 mA |
| Current output, no-load voltage, max. | 20 V |
| Output ranges, voltage |
| 0 to 10 V | Yes |
| 1 to 5 V | Yes |
| -10 to +10 V | Yes |
| Output ranges, current |
| 0 to 20 mA | Yes |
| -20 to +20 mA | Yes |
| 4 to 20 mA | Yes |
| Connection of actuators |
| for voltage output 2-conductor connection | Yes |
| for current output 2-conductor connection | Yes |
| Load impedance (in rated range of output) |
| with voltage outputs, min. | 1 kΩ |
| with voltage outputs, capacitive load, max. | 1 µF |
| with current outputs, max. | 600 Ω |
| with current outputs, inductive load, max. | 1 mH |
| Destruction limits against externally applied voltages and currents |
| Voltages at the outputs towards MANA | 28.8 V permanent, 35 V for max. 500 ms |
| Cable length |
| Cable length, shielded, max. | 30 m |
| Analog value creation |
| Analog value display | SIMATIC S7 format |
| Measurement principle | Resistor network |
| Integrations and conversion time/ resolution per channel |
| Resolution (incl. overrange) | 15 bits + sign |
| Conversion time (per channel) | 1 ms |
| Settling time |
| for resistive load | 2 ms |
| for capacitive load | 1.8 ms |
| for inductive load | 2 ms |
| Errors/accuracies |
| Output ripple (based on output area, bandwidth 0 to 50 kHz) | U: ±0.6 mVrms; I: ±0.4 nArms |
| Linearity error (relative to output area) | +/- 0,02 % |
| Temperature error (relative to output area) | U: 0.001%/°C; I: 0.0025%/°C |
| Crosstalk between the outputs, min. | 70 dB |
| Repeat accuracy in settled status at 25 °C (relative to output area) | +/- 0,008 % |
| Interfaces |
| Transmission procedure | 100BASE-TX |
| Transmission rate, max. | 100 Mbit/s |
| Supports protocol for PROFINET IO |
| Number of PROFINET interfaces | 2 |
| Autocrossing | Yes |
| Automatic detection of transmission speed | Yes |
| Integrated switch | Yes |
| PROFINET IO Device |
| IRT with the option "high flexibility" supported | Yes |
| Prioritized startup supported | Yes |
| Protocols |
| Supports protocol for PROFINET IO | Yes |
| Protocols (Ethernet) |
| SNMP | Yes |
| DCP | Yes |
| LLDP | Yes |
| ping | Yes |
| arp | Yes |
| Interrupts/diagnostics/status information |
| Status indicator | Yes |
| Substitute values connectable | Yes |
| Alarms |
| Diagnostic alarm | Yes |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostic information readable | Yes |
| Monitoring the supply voltage | Yes; Green "ON" LED |
| Wire break | Yes; Channel-by-channel with current output |
| Short circuit | Yes; Channel-by-channel with voltage output |
| Group error | Yes; Red/yellow "SF/MT" LED |
| Galvanic isolation |
| between the load voltages | Yes |
| between load voltage and all other switching components | No |
| between Ethernet and electronics | Yes |
| Galvanic isolation analog outputs |
| between the channels | No |
| Permissible potential difference |
| between M internally and the outputs | 10 Vpp AC |
| Degree and class of protection |
| IP65 | Yes |
| IP66 | Yes |
| IP67 | Yes |
| Connection method |
| M12 | Yes |
| Dimensions |
| Width | 60 mm |
| Height | 175 mm |
| Depth | 49 mm |
| Weight |
| Weight | 930 g |
| Status | Mar 12, 2012 |