| | SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67 |
| |
| General information |
| Vendor identification (VendorID) | 002AH |
| Device identifier (DeviceID) | 0306H |
| Supply voltage |
| 24 V DC | Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current |
| Current consumption, typ. | 110 mA |
| Encoder supply |
| Number of outputs | 4 |
| 24 V encoder supply |
| Short-circuit protection | Yes; Electronic at 1.4 A |
| Output current, max. | 1 A |
| Power losses |
| Power loss, typ. | 2.8 W |
| Analog inputs |
| Number of analog inputs | 8 |
| Number of analog inputs for voltage/current measurement | 4 |
| Number of analog inputs for resistance/resistance thermometer measurement | 4 |
| permissible input voltage for voltage input (destruction limit), max. | 28.8 V permanent, 35 V for max. 500 ms |
| Input ranges (rated values), voltages |
| 0 to +10 V | Yes |
| 1 to 5 V | Yes |
| -10 V to +10 V | Yes |
| -80 mV to +80 mV | Yes |
| Input ranges (rated values), currents |
| 0 to 20 mA | Yes |
| -20 to +20 mA | Yes |
| 4 to 20 mA | Yes |
| Input ranges (rated values), thermoelements |
| Type E | Yes |
| Type J | Yes |
| Type K | Yes |
| Type N | Yes |
| Input ranges (rated values), resistance thermometers |
| Ni 100 | Yes |
| Ni 1000 | Yes |
| Ni 120 | Yes |
| Ni 200 | Yes |
| Ni 500 | Yes |
| Pt 100 | Yes |
| Pt 1000 | Yes |
| Pt 200 | Yes |
| Pt 500 | Yes |
| Input ranges (rated values), resistors |
| 0 to 150 ohms | Yes |
| 0 to 300 ohms | Yes |
| 0 to 600 ohms | Yes |
| 0 to 3000 ohms | Yes |
| Thermocouple (TC) |
| Temperature compensation |
| Parameterizable | Yes |
| internal temperature compensation | Yes |
| external temperature compensation with compensations socket | Yes |
| Cable length |
| Cable length, shielded, max. | 30 m |
| Analog value creation |
| Analog value display | SIMATIC S7 format |
| Measurement principle | integrating |
| Integrations and conversion time/ resolution per channel |
| Resolution (incl. overrange) | 15 bits + sign |
| Integration time, parameterizable | Yes |
| Integration time, ms | 2/16.67/20/100 ms |
| Interference voltage suppression for interference frequency f1 in Hz | 500 / 60 / 50 / 10 Hz |
| Conversion time (per channel) | 4/19/22/102 ms |
| Smoothing of measured values |
| Parameterizable | Yes |
| Step: None | Yes; 1 x cycle time |
| Step: low | Yes; 4 x cycle time |
| Step: Medium | Yes; 16 x cycle time |
| Step: High | Yes; 64 x cycle time |
| Encoder |
| Number of connectable encoders, max. | 8 |
| Connection of signal encoders |
| for voltage measurement | Yes |
| for current measurement as 2-wire transducer | Yes |
| for current measurement as 4-wire transducer | Yes |
| for resistance measurement with 2-conductor connection | Yes |
| for resistance measurement with 3-conductor connection | Yes |
| for resistance measurement with 4-conductor connection | Yes |
| Errors/accuracies |
| Linearity error (relative to input area) | +/- 0,01 % |
| Temperature error (relative to input area) | U: 0.0035%/°C; I:0.006%/°C; RTD: 0.0005%/°C; TC: 0.0035%/°C |
| Crosstalk between the inputs, min. | 85 dB |
| Repeat accuracy in settled status at 25 °C (relative to input area) | +/- 0,008 % |
| Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
| Series mode interference (peak value of interference < rated value of input range), min. | 46 dB |
| Common mode interference, min. | 70 dB |
| Interfaces |
| Transmission procedure | 100BASE-TX |
| Transmission rate, max. | 100 Mbit/s |
| Supports protocol for PROFINET IO |
| Number of PROFINET interfaces | 2 |
| Autocrossing | Yes |
| Automatic detection of transmission speed | Yes |
| Integrated switch | Yes |
| PROFINET IO Device |
| IRT with the option "high flexibility" supported | Yes |
| Prioritized startup supported | Yes |
| Protocols |
| Supports protocol for PROFINET IO | Yes |
| Protocols (Ethernet) |
| SNMP | Yes |
| DCP | Yes |
| LLDP | Yes |
| ping | Yes |
| arp | Yes |
| Interrupts/diagnostics/status information |
| Alarms |
| Diagnostic alarm | Yes |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostic information readable | Yes |
| Monitoring the supply voltage | Yes; Green "ON" LED |
| Short circuit encoder supply | Yes; per module |
| Group error | Yes; Red/yellow "SF/MT" LED |
| Overflow/underflow | Yes |
| Galvanic isolation |
| between the load voltages | Yes |
| between load voltage and all other switching components | No |
| between Ethernet and electronics | Yes |
| Назад в раздел
|