| | SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 4 AI RTD HIGH FEATURE, PT100; PT200; PT500; PT1000; NI100; NI200; NI500; NI1000; CHANNEL DIANOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY |
| |
| Supply voltage |
| Load voltage L+ |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes; against destruction |
| Input current |
| from backplane bus 3.3 V DC, max. | 10 mA; typ. |
| Power losses |
| Power loss, typ. | 0.7 W |
| Address area |
| Address space per module |
| Address space per module, max. | 8 byte |
| Analog inputs |
| Number of analog inputs | 4 |
| Cycle time (all channels) max. | 83 ms; 83 ms at 50 Hz; 69 ms at 60 Hz |
| Technical unit for temperature measurement adjustable | Yes |
| Input ranges |
| Voltage | No |
| Current | No |
| Thermocouple | No |
| Resistance thermometer | Yes |
| Resistance | Yes |
| Input ranges (rated values), resistance thermometers |
| Cu 10 | No |
| Ni 100 | Yes |
| Input resistance (Ni 100) | 10000 kΩ |
| Ni 1000 | Yes |
| Input resistance (Ni 1000) | 10000 kΩ |
| Ni 120 | Yes |
| Input resistance (Ni 120) | 10000 kΩ |
| Ni 200 | Yes |
| Input resistance (Ni 200) | 10000 kΩ |
| Ni 500 | Yes |
| Input resistance (Ni 500) | 10000 kΩ |
| Pt 100 | Yes |
| Input resistance (Pt 100) | 10000 kΩ |
| Pt 1000 | Yes |
| Input resistance (Pt 1000) | 10000 kΩ |
| Pt 200 | Yes |
| Input resistance (Pt 200) | 10000 kΩ |
| Pt 500 | Yes |
| Input resistance (Pt 500) | 10000 kΩ |
| Input ranges (rated values), resistors |
| 0 to 150 ohms | Yes |
| Input resistance (0 to 150 ohms) | 10000 kΩ |
| 0 to 300 ohms | Yes |
| Input resistance (0 to 300 ohms) | 10000 kΩ |
| 0 to 600 ohms | Yes |
| Input resistance (0 to 600 ohms) | 10000 kΩ |
| 0 to 3000 ohms | Yes |
| Input resistance (0 to 3000 ohms) | 10000 kΩ |
| Resistance thermometer (RTD) |
| Characteristic linearization |
| for resistance thermometer | Ptxxx, Nixxx |
| Characteristic linearization |
| Parameterizable | Yes |
| Cable length |
| Cable length, shielded, max. | 30 m |
| Analog value creation |
| Measurement principle | integrating |
| Integrations and conversion time/ resolution per channel |
| Resolution with overrange (bit including sign), max. | 15 bit; at 150, 300, 600 und 3000 ohms; otherwise 15 bits + sign |
| Integration time, ms | 20 / 16,667 |
| Interference voltage suppression for interference frequency f1 in Hz | 50/60 Hz |
| Conversion time (per channel) | 20.625 ms; 20.625 ms at 50 Hz; 17.25 ms at 60 Hz |
| Smoothing of measured values |
| Parameterizable | Yes |
| Step: None | Yes; 1 x cycle time |
| Step: low | Yes; 4 x cycle time |
| Step: Medium | Yes; 16 x cycle time |
| Step: High | Yes; 64 x cycle time |
| Encoder |
| Connection of signal encoders |
| for resistance measurement with 2-conductor connection | Yes; Line resistances are also measured |
| for resistance measurement with 3-conductor connection | Yes |
| for resistance measurement with 4-conductor connection | Yes |
| Errors/accuracies |
| Linearity error (relative to input area) | +/- 0.05 % |
| Temperature error (relative to input area) | +/- 0.002 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in settled status at 25 °C (relative to input area) | +/- 0.015 % |
| Operational limit in overall temperature range |
| Resistance-type thermometer, relative to input area | +/- 0.175 % |
| Basic error limit (operational limit at 25 °C) |
| Resistance-type thermometer, relative to input area | +/- 0.125 % |
| Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
| Series mode interference (peak value of interference < rated value of input range), min. | 50 dB |
| common mode voltage (USS < 2.5 V) , min. | 70 dB; Interference voltage < 5 V |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Wire break | Yes |
| Group error | Yes |
| Overflow/underflow | Yes |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Parameter |
| Diagnosis: wire break | 1 |
| Load voltage | No |
| Measurement type/range | R4L / R3L / R2L/ TR4L / TR3L / TR2L |
| Interference frequency suppression | 50/60 Hz |
| Group diagnostics | 1 |
| Overflow/underflow | 1 |
| Unit | Degrees C / Degrees F |
| Galvanic isolation |
| Galvanic isolation analog inputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| Permissible potential difference |
| between the inputs (UCM) | 5 Vpp AC |
| between MANA and M internally (UISO) | 500 V DC |
| Isolation |
| Isolation checked with | Назад в раздел
|