6ES7144-1JB31-0XB0 - SIMATIC DP, EXPANSION MODULE EM 144 FOR ET 200X, IP66/67 2AI, PT100, 12 BIT+SIGN, WITH DIAGNOSIS BY CHANNEL 2/3/4-WIRE CONNECTION (siemens) - Quad Industry GmbH

Артикул: 6ES7144-1JB31-0XB0
Наименование: SIMATIC DP, EXPANSION MODULE EM 144 FOR ET 200X, IP66/67 2AI, PT100, 12 BIT+SIGN, WITH DIAGNOSIS BY CHANNEL 2/3/4-WIRE CONNECTION (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, EXPANSION MODULE EM 144 FOR ET 200X, IP66/67 2AI, PT100, 12 BIT+SIGN, WITH DIAGNOSIS BY CHANNEL 2/3/4-WIRE CONNECTION
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1998-07-01 2007-10-01 2008-10-01
SIMATIC DP, EXPANSION MODULE EM 144 FOR ET 200X, IP66/67 2AI, PT100, 12 BIT+SIGN, WITH DIAGNOSIS BY CHANNEL 2/3/4-WIRE CONNECTION
Input current
from backplane bus 5 V DC, max. 40 mA
Power losses
Power loss, max. 0.9 W
Analog inputs
Number of analog inputs 2
permissible input voltage for voltage input (destruction limit), max. 30 V
Constant measurement current for resistance-type transmitter, typ. 1.5 mA
Input ranges
Resistance thermometer Yes
Input ranges (rated values), resistance thermometers
Pt 100 Yes; Standard
Input resistance (Pt 100) 10 MΩ
Characteristic linearization
Parameterizable Yes
Cable length
Cable length, shielded, max. 30 m
Analog value creation
Analog value display (parameterizable) Yes; S7 Format / S5 Format
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 12 bit; + sign; overrange 17.5%
Integration time, parameterizable Yes
Integration time, ms 16.7 / 20 ms
Encoder
Connection of signal encoders
for resistance measurement with 2-conductor connection Yes
for resistance measurement with 3-conductor connection Yes
for resistance measurement with 4-conductor connection Yes
Errors/accuracies
Operational limit in overall temperature range
Voltage, relative to input area +/- 1,2 %
Current, relative to input area +/- 1,2 %
Resistance-type thermometer, relative to input area +/- 1,2 %
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm Yes
Limit value alarm Yes; upper limit, channel by channel/ lower limit channel by channel
Hardware interrupt Yes
Diagnostic messages
Diagnostics Yes
Wire break Yes; channel by channel
Overflow/underflow Yes; channel by channel
Diagnostics indication LED
Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog inputs
Galvanic isolation analog inputs No
Connection method
Inputs/outputs 4/5-pin M12 circular connectors
Dimensions
Width 87 mm; Width module 60 mm
Height 110 mm
Depth 55 mm
Weight
Weight, approx. 250 g