| | SIMATIC DP, DISTRIBUTED I/O ET200X:EXT.MODULE BM143/DESINA 8DI/DO CONFIGURABLE,ADD.DIAG- INPUTS, IP67 |
| |
| Input current |
| from backplane bus 5 V DC, max. | 40 mA |
| Encoder supply |
| Output current |
| up to 40 °C, max. | 1 A |
| up to 55 °C, max. | 0.8 A |
| Power losses |
| Power loss, typ. | 1.5 W |
| Digital inputs |
| Number/binary inputs | 8; 8 function inputs (diagnostic inputs or inputs with opener function) |
| Input characteristic curve acc. to IEC 61131, Type 2 | Yes |
| Number of simultaneously controllable inputs | 8 |
| Input voltage |
| Rated value, DC | 24 V; Input voltage for parameterized DI (Pin 4) / Input voltage for function input (Pin 2) |
| for signal "0" | -30 to +5 V |
| for signal "1" | 13 to 30 V |
| Input current |
| for signal "1", typ. | 5 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| at "0" to "1", min. | 1.2 ms |
| at "0" to "1", max. | 4.8 ms |
| Cable length |
| Cable length unshielded, max. | 30 m; for signal lines |
| Digital outputs |
| Number/binary outputs | 8; 8 process channels, parameterization as DI/DO; 8 function channels, parameter assignment as diagnostics/NC input |
| Functionality/short-circuit strength | Yes; Electronic |
| Response threshold, typ. | 1.8 A |
| Output current |
| for signal "1" rated value | 1.2 A |
| for signal "1" permissible range for 0 to 60 °C, min. | 5 mA |
| for signal "1" permissible range for 0 to 60 °C, max. | 1.3 A |
| for signal "0" residual current, max. | 0.5 mA |
| Switching frequency |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 2 Hz |
| on lamp load, max. | 1 Hz |
| Cable length |
| Cable length unshielded, max. | 30 m; for signal lines |
| Encoder |
| Connectable encoders |
| 2-wire sensor | Yes |
| Permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Interrupts/diagnostics/status information |
| Diagnostics indication LED |
| Status indicator per channel (yellow) | Yes |
| Indicator function input per channel (yellow/red) | Yes |
| Galvanic isolation |
| Galvanic isolation digital inputs |
| between the channels and the backplane bus | No |
| Galvanic isolation digital outputs |
| between the channels and the backplane bus | No |
| Dimensions |
| Width | 87 mm; Width module 60 mm |
| Height | 180 mm |
| Depth | 55 mm |
| Status | Mar 12, 2012 |