| | SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 8 DO DC 24V, 0.5A MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY |
| |
| FH technology |
| Module for failsafe applications | No |
| Supply voltage |
| Load voltage 2L+ |
| Rated value (DC) | 24 V |
| Short-circuit protection | Yes; per channel, electronic |
| Reverse polarity protection | Yes; against destruction; load increasing |
| Input current |
| from load voltage 2L+ (without load), max. | 30 mA |
| from backplane bus 3.3 V DC, max. | 30 mA |
| Power losses |
| Power loss, typ. | 2 W |
| Address area |
| Address space per module |
| with packing | 8 bit |
| without packing | 1 byte |
| Digital outputs |
| Number/binary outputs | 8 |
| Functionality/short-circuit strength | Yes; per channel, electronic |
| Response threshold, typ. | 0,7 |
| Limitation of inductive shutdown voltage to | 2L+ (-47 V) |
| Lamp load, max. | 5 W |
| Controlling a digital input | Yes; Isolation between 1L+ and 2L+ is no longer provided, as 1M and 2M are jumpered |
| Load resistance range |
| lower limit | 48 Ω |
| upper limit | 4 kΩ |
| Output voltage |
| for signal "1", min. | 2L+ (-0.8 V) |
| Output current |
| for signal "1" rated value | 0.5 A |
| for signal "0" residual current, max. | 0.5 mA |
| Parallel switching of 2 outputs |
| for increased power | No |
| for redundant control of a load | Yes |
| Switching frequency |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 1 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 55 °C, max. | 4 A |
| Cable length |
| Cable length, shielded, max. | 30 m |
| Cable length unshielded, max. | 30 m |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostic information readable | Yes |
| Short circuit | Yes; Short-circuit of outputs to ground; module by module |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Status indicator digital output (green) | Yes |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| Isolation |
| Isolation checked with | 500 V DC |
| Dimensions |
| Width | 45 mm |
| Height | 130 mm |
| Depth | 35 mm |
| Weight |
| Weight, approx. | 140 g |
| Status | Mar 12, 2012 |