| | SIMATIC DP, ELECTRONIC MODULE FOR ET200PRO 16 DI DC 24V, MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE CONNECTING MODULE IO 6ES7194-4CB50-0AA0 MUST BE ORDERED SEPERATELY |
| |
| Supply voltage |
| 24 V DC | Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity |
| Input current |
| from backplane bus 3.3 V DC, max. | 20 mA |
| from supply voltage 1L+, max. | 30 mA |
| Encoder supply |
| Number of outputs | 8 |
| Output current |
| up to 55 °C, max. | 1 A |
| Short-circuit protection | Yes; per module, electronic |
| Power losses |
| Power loss, typ. | 3 W |
| Address area |
| Occupied address area |
| Inputs | 2 byte |
| Digital inputs |
| Number/binary inputs | 16 |
| Input characteristic curve acc. to IEC 61131, Type 1 | Yes |
| Number of simultaneously controllable inputs |
| all mounting positions |
| up to 55 °C, max. | 16 |
| Input voltage |
| Rated value, DC | 24 V |
| for signal "0" | -3 to +5 V |
| for signal "1" | 11 to 30 V |
| Input current |
| for signal "1", typ. | 4 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| Parameterizable | No |
| at "0" to "1", min. | 1.2 ms |
| at "0" to "1", max. | 4.8 ms |
| at "1" to "0", min. | 0.7 ms |
| at "1" to "0", max. | 3 ms |
| Cable length |
| Cable length, shielded, max. | 30 m |
| Cable length unshielded, max. | 30 m |
| Encoder |
| Connectable encoders |
| 2-wire sensor | Yes |
| Permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostic information readable | Yes |
| Short circuit | Yes; Sensor supply to M; module by module |
| Group error | Yes |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Status indicator digital input (green) | Yes; Per channel |
| Galvanic isolation |
| between backplane bus and all other circuit components | Yes |
| Galvanic isolation digital inputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| Permissible potential difference |
| between different circuits | 75 VDC / 60 VAC |
| Isolation |
| Isolation checked with | 500 V DC |
| Degree and class of protection |
| IP67 | Yes |
| Dimensions |
| Width | 45 mm |
| Height | 130 mm |
| Depth | 35 mm |
| Weight |
| Weight, approx. | 140 g |
| Status | Mar 12, 2012 |