| | SIMATIC DP, BASIC MODULE BM141 ET 200ECO: 16DI 24V DC; 8 X M12,DOUBLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY |
| |
| General information |
| Vendor identification (VendorID) | 80DAh |
| Supply voltage |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current |
| from supply voltage 1L+, max. | 70 mA; typ. |
| Encoder supply |
| Number of outputs | 8 |
| Output voltage | 24 V DC |
| Output current, rated value | 1 A; Aggregate current up to 55 °C |
| Output current |
| Short-circuit protection | Yes; Electronic |
| Power losses |
| Power loss, typ. | 3.6 W |
| Digital inputs |
| Number/binary inputs | 16 |
| Input characteristic curve acc. to IEC 61131, Type 1 | Yes |
| Number of simultaneously controllable inputs | 16; All mounting positions up to 55 °C |
| Input voltage |
| Type of input voltage | DC |
| Rated value, DC | 24 V |
| for signal "0" | -3 to +5 V |
| for signal "1" | 13 to 30 V |
| Input current |
| for signal "1", typ. | 7 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| at "0" to "1", max. | 3 ms; typ. |
| at "1" to "0", max. | 3 ms; typ. |
| Cable length |
| Cable length unshielded, max. | 30 m |
| Encoder |
| Connectable encoders |
| 2-wire sensor | Yes |
| Permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 12 Mbit/s; 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 3 / 6 / 12 Mbit/s |
| Protocols |
| Further protocols |
| PROFIBUS DP protocol | Yes |
| Interrupts/diagnostics/status information |
| Status indicator | Yes |
| Alarms |
| Alarms | No |
| Diagnostic messages |
| Diagnostics | Yes; Diagnostic information readable |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Status indicator digital input (green) | Yes |
| Channel error indicator F (red) | No |
| Galvanic isolation |
| between PROFIBUS DP and all other circuit components | Yes |
| Galvanic isolation digital inputs |
| between the channels | No |
| Permissible potential difference |
| between different circuits | 75 VDC / 60 VAC |
| Isolation |
| Isolation checked with | 500 V DC |
| Dimensions |
| Width | 60 mm |
| Height | 210 mm |
| Depth | 28 mm |
| Weight |
| Weight, approx. | 210 g |
| Status | Mar 12, 2012 |