6ES7135-7TD00-0AB0 - SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AO HART, 4 - 20MA, FOR CONNECTION OF HART FIELD DEVICES (siemens) - Quad Industry GmbH

Артикул: 6ES7135-7TD00-0AB0
Наименование: SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AO HART, 4 - 20MA, FOR CONNECTION OF HART FIELD DEVICES (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AO HART, 4 - 20MA, FOR CONNECTION OF HART FIELD DEVICES
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2004-10-15
Manuals weitere>>
Устройство децентрализованной периферии ET 200 iSP  2007-03-14
SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AO HART, 4 - 20MA, FOR CONNECTION OF HART FIELD DEVICES
Input current
from load voltage1L+, max. 330 mA
Power losses
Power loss, max. 2.7 W
Analog outputs
Number of analog outputs 4
Cycle time (all channels) max. 3.6 ms
Output ranges, current
4 to 20 mA Yes
Connection of actuators
for current output 2-conductor connection Yes
Load impedance (in rated range of output)
with current outputs, max. 750 Ω
Cable length
Cable length, shielded, max. 500 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 14 bit
Settling time
for resistive load 4 ms
for capacitive load 40 ms
for inductive load 40 ms
Errors/accuracies
Linearity error (relative to output area) +/- 0.015 %
Temperature error (relative to output area) +/- 0.005 %/K
Crosstalk between the outputs, min. -50 dB
Repeat accuracy in settled status at 25 °C (relative to output area) +/- 0.01 %
Operational limit in overall temperature range
Current, relative to output area +/- 0.15 %
Basic error limit (operational limit at 25 °C)
Current, relative to output area +/- 0.1 %
Interrupts/diagnostics/status information
Substitute values connectable Yes
Alarms
Diagnostic alarm Yes
Diagnostic messages
Diagnostic information readable Yes
Wire break Yes
Short circuit Yes
Diagnostics indication LED
Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog outputs
between the channels No
between the channels and the backplane bus Yes
Standards, approvals, certificates
CE mark Yes
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC) II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
Type of protection acc. to KEMA 04 ATEX 1250
Dimensions
Width 30 mm
Height 129 mm
Depth 136.5 mm
Weight
Weight, approx. 265 g