| | SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S |
| |
| Supply voltage |
| Rated value (DC) | 24 V; Value at t < 0.5 s: 35 V |
| permissible range, lower limit (DC) | 18.5 V |
| permissible range, upper limit (DC) | 30.2 V |
| Input current |
| from supply voltage L+, max. | 200 mA; Logic |
| Power losses |
| Power loss, typ. | 2.4 W |
| Hardware configuration |
| Rack |
| Required terminal block | TB8 |
| Digital outputs |
| Load resistance range |
| Load impedance in rated range of output , capacitive load, max. | 1 µF |
| Analog outputs |
| Number of analog outputs | 4 |
| Voltage output, short-circuit protection | Yes; Electronic; max. 1 output in parallel |
| Voltage output, short-circuit current, max. | 25 mA |
| Current output, no-load voltage, max. | 18 V |
| Output ranges, voltage |
| 0 to 10 V | Yes |
| -10 to +10 V | Yes |
| Output ranges, current |
| 0 to 20 mA | Yes |
| 4 to 20 mA | Yes |
| Connection of actuators |
| for voltage output 2-conductor connection | Yes |
| for voltage output 4-conductor connection | Yes |
| for current output 2-conductor connection | Yes |
| Load impedance (in rated range of output) |
| with current outputs, max. | 300 Ω |
| with current outputs, inductive load, max. | 1 mH |
| Cable length |
| Cable length, shielded, max. | 100 m |
| Analog value creation |
| Integrations and conversion time/ resolution per channel |
| Resolution with overrange (bit including sign), max. | 11 bit; Two's complement |
| Conversion time (per channel) | 1 ms |
| Settling time |
| for resistive load | 0.1 ms |
| for capacitive load | 3.3 ms |
| for inductive load | 0.5 ms |
| Errors/accuracies |
| Output ripple (based on output area, bandwidth 0 to 50 kHz) | +/- 0.05 % |
| Linearity error (relative to output area) | +/- 0.05 % |
| Temperature error (relative to output area) | +/- 0.02 % |
| Crosstalk between the outputs, min. | 40 dB |
| Repeat accuracy in settled status at 25 °C (relative to output area) | +/- 0.05 % |
| Operational limit in overall temperature range |
| Voltage, relative to output area | +/- 0.05 % |
| Current, relative to output area | +/- 1 % |
| Basic error limit (operational limit at 25 °C) |
| Voltage, relative to output area | +/- 0.2 % |
| Current, relative to output area | +/- 0.3 % |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 12 Mbit/s |
| Communication functions |
| Bus protocol/transmission protocol | PROFIBUS DP |
| Interrupts/diagnostics/status information |
| Alarms |
| Diagnostic alarm | Yes; Parameterizable |
| Diagnostics indication LED |
| Bus fault BF (red) | Yes |
| Run mode RUN (green) | Yes |
| Galvanic isolation |
| between electronic block and PROFIBUS DP | Yes |
| Galvanic isolation analog outputs |
| Galvanic isolation analog outputs | No |
| Ambient conditions |
| Operating temperature |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C; 40°C for other mountings |
| Air pressure |
| permissible range, min. | 795 hPa |
| permissible range, max. | 1080 hPa |
| Relative humidity |
| Operation, min. | 15 % |
| Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Degree and class of protection |
| IP20 | Yes |
| Connection method |
| Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Dimensions |
| Width | 160 mm; EB and TB |
| Height | 130 mm; EB and TB |
| Depth | 60 mm; EB and TB |
| Weight |
| Weight, approx. | 550 g; EB and TB |
| Status | Feb 27, 2012 |