| SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI, TC, FOR CONNECTION OF THERMOELEMENS (VOLTAGE MEASUREMENT) |
|
Input current |
from supply voltage L+, max. | 30 mA |
Power losses |
Power loss, typ. | 0.4 W |
Analog inputs |
Number of analog inputs | 4 |
Cycle time (all channels) max. | 320 ms; 66 ms basic conversion time x 4 channels with 60 Hz interference frequency suppression; 80 ms basic conversion time x 4 channels with 50 Hz interference frequency suppression |
Technical unit for temperature measurement adjustable | Yes |
Input ranges |
Voltage | Yes |
Current | No |
Thermocouple | Yes |
Resistance thermometer | No |
Resistance | No |
Input ranges (rated values), voltages |
-80 mV to +80 mV | Yes |
Input resistance (-80 mV to +80 mV) | 1000 kΩ |
Input ranges (rated values), thermoelements |
Type B | Yes |
Input resistance (Type B) | 1000 kΩ |
Type C | Yes |
Input resistance (Type C) | 1000 kΩ |
Type E | Yes |
Input resistance (Type E) | 1000 kΩ |
Type J | Yes |
Input resistance (type J) | 1000 kΩ |
Type K | Yes |
Input resistance (Type K) | 1000 kΩ |
Type L | Yes |
Input resistance (Type L) | 1000 kΩ |
Type N | Yes |
Input resistance (Type N) | 1000 kΩ |
Type R | Yes |
Input resistance (Type R) | 1000 kΩ |
Type S | Yes |
Input resistance (Type S) | 1000 kΩ |
Type T | Yes |
Input resistance (Type T) | 1000 kΩ |
Type U | Yes |
Input resistance (Type U) | 1000 kΩ |
Thermocouple (TC) |
for thermocouples | 1 |
Temperature compensation |
internal temperature compensation | Yes; via supplied TC sensor module |
external temperature compensation with compensations socket | Yes; via temperature value, acquired by an analog module of the same ET 200iSP station |
Characteristic linearization |
Parameterizable | Yes |
Cable length |
Cable length, shielded, max. | 50 m |
Analog value creation |
Measurement principle | integrating (Sigma-Delta) |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit |
Integration time, parameterizable | Yes |
Basic conversion time, including integration time, ms | 80 ms at 50 Hz; 66 ms at 60 Hz |
additional conversion time for wire break monitoring | 5 |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Smoothing of measured values |
Parameterizable | Yes; in 4 stages |
Step: None | Yes; 1 x cycle time |
Step: low | Yes; 4 x cycle time |
Step: Medium | Yes; 32 x cycle time |
Step: High | Yes; 64 x cycle time |
Errors/accuracies |
Linearity error (relative to input area) | +/- 0.015 % |
Temperature error (relative to input area) | +/- 0.02 % |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in settled status at 25 °C (relative to input area) | +/- 0.01 % |
Operational limit in overall temperature range |
Voltage, relative to input area | +/- 0.15 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input area | +/- 0.1 % |
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
Common mode interference, min. | 90 dB |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | Yes; Parameterizable |
Limit value alarm | Yes; Parameterizable |
Diagnostic messages |
Diagnostic information readable | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
between the channels | Yes; Functional, yes |
between the channels and the backplane bus | Yes |
Standards, approvals, certificates |
CE mark | Yes |
Use in hazardous areas |
Type of protection acc. to EN 50020 (CENELEC) | II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I |
Type of protection acc. to KEMA | 04 ATEX 1246 |
Dimensions |
Width | 30 mm |
Height | 129 mm |
Depth | 136.5 mm |
Weight |
Weight, approx. | 230 g |
Status | Mar 12, 2012 |