| | SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET200B, W=235MM, 8DI/8RO, 120/230V AC, APPLICABLE ON TB6/AC |
| |
| Hardware configuration |
| Rack |
| Required terminal block | TB6/AC |
| Digital inputs |
| Number/binary inputs | 8 |
| Input voltage |
| Rated value, AC | 120/230 V AC |
| for signal "0" | 0 to 40 V |
| for signal "1" | 79 to 264 V |
| Input current |
| for signal "1", typ. | 3 mA; 3 to 16 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| at "0" to "1", min. | 0 ms |
| at "0" to "1", max. | 25 ms |
| Cable length |
| Cable length unshielded, max. | 600 m |
| Digital outputs |
| Number/binary outputs | 8; 2 high and 6 low current relays |
| Functionality/short-circuit strength | Yes; Electronic |
| Output voltage |
| Rated value (AC) | 120/230 V AC |
| Rated value (DC) | 24 to 150 V DC |
| Output current |
| for signal "1" permissible range for 0 to 60 °C, min. | 4 A; 4 A (2 ports); 2 A (6 ports) |
| Switching frequency |
| with resistive load, max. | 10 Hz |
| with inductive load, max. | 2 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 60 °C, max. | 2 A |
| Cable length |
| Cable length unshielded, max. | 100 m |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 12 Mbit/s |
| Galvanic isolation |
| between electronic block and PROFIBUS DP | Yes |
| Galvanic isolation digital inputs |
| Galvanic isolation digital inputs | Yes |
| Galvanic isolation digital outputs |
| Galvanic isolation digital outputs | Yes |
| Ambient conditions |
| Operating temperature |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C; 40°C for other mountings |
| Air pressure |
| permissible range, min. | 795 hPa |
| permissible range, max. | 1080 hPa |
| Relative humidity |
| Operation, min. | 15 % |
| Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Degree and class of protection |
| IP20 | Yes |
| Connection method |
| Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Status | Mar 5, 2012 |