| | SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 24DI 24V DC, 8DO 24V DC, 0.5A, 0.2MS INPUT DELAY, STANDARD |
| |
| Hardware configuration |
| Rack |
| Required terminal block | TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC |
| Digital inputs |
| Number/binary inputs | 24 |
| Input voltage |
| Rated value, DC | 24 V |
| for signal "0" | -30 to +5 V |
| for signal "1" | 13 to 30 V |
| Input current |
| for signal "1", typ. | 4 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| at "0" to "1", max. | 0.2 ms |
| Cable length |
| Cable length unshielded, max. | 100 m |
| Digital outputs |
| Number/binary outputs | 8 |
| Functionality/short-circuit strength | Yes; Electronic |
| Output voltage |
| Rated value (DC) | 24 V |
| for signal "0", max. | 2 V; Idling |
| for signal "1", min. | UE -3 V |
| Output current |
| for signal "1" permissible range for 0 to 60 °C, min. | 0.5 A; in one group |
| for signal "0" residual current, max. | 1 mA |
| Switching frequency |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 8 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 60 °C, max. | 2 A |
| Cable length |
| Cable length unshielded, max. | 100 m |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 12 Mbit/s |
| Galvanic isolation |
| between electronic block and PROFIBUS DP | Yes |
| Galvanic isolation digital inputs |
| Galvanic isolation digital inputs | No |
| Galvanic isolation digital outputs |
| Galvanic isolation digital outputs | Yes |
| Ambient conditions |
| Operating temperature |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C; 40°C for other mountings |
| Air pressure |
| permissible range, min. | 795 hPa |
| permissible range, max. | 1080 hPa |
| Relative humidity |
| Operation, min. | 15 % |
| Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Degree and class of protection |
| IP20 | Yes |
| Connection method |
| Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Status | Mar 5, 2012 |