| | SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8DE 24V DC; 8DA 24V DC, 0,5A WITH INTEGRATED HW SWITCH-OFF OF THE OUTPUTS |
| |
| Supply voltage |
| 24 V DC | Yes; L1+, L3+; value at t < 0.5 s: 35 V |
| permissible range, lower limit (DC) | 18.5 V |
| permissible range, upper limit (DC) | 30.2 V |
| Input current |
| Current consumption, typ. | 70 mA; from L3+; logic |
| Current consumption, max. | 500 mA; from L3+; sensor |
| I²t | 0.05 A²·s; with starting current inrush |
| Power losses |
| Power loss, max. | 3.8 W |
| Hardware configuration |
| Rack |
| Required terminal block | TB1/DC, TB1-4/DC, TB3/DC |
| Digital inputs |
| Number/binary inputs | 8 |
| Input voltage |
| Rated value, DC | 24 V |
| for signal "0" | -30 to +5 V |
| for signal "1" | 13 to 30 V |
| Input current |
| for signal "1", typ. | 4 mA; At 24 V min. 2 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| at "0" to "1", min. | 3 ms |
| Cable length |
| Cable length unshielded, max. | 100 m |
| Digital outputs |
| Number/binary outputs | 8 |
| Functionality/short-circuit strength | Yes; Electronic |
| Limitation of inductive shutdown voltage to | typically (L1+) -55 V |
| Lamp load, max. | 5 W |
| Controlling a digital input | Yes |
| Output voltage |
| Rated value (DC) | 24 V |
| for signal "0", max. | 2 V; Idling |
| for signal "1", min. | UE -3 V |
| Output current |
| for signal "1" permissible range for 0 to 60 °C, min. | 0.5 A; in one group |
| for signal "0" residual current, max. | 1 mA |
| Output delay with resistive load |
| 0 to "1", max. | 50 ms |
| 1 to "0", max. | 100 ms |
| Switching frequency |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 8 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 60 °C, max. | 2 A |
| Cable length |
| Cable length unshielded, max. | 100 m |
| Encoder |
| Connectable encoders |
| 2-wire BEROS | Yes |
| permissible quiescent current (2-wire BEROS), max. | 1.5 mA |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 12 Mbit/s |
| SYNC capability | Yes |
| FREECE capability | Yes |
| Communication functions |
| Bus protocol/transmission protocol | PROFIBUS DP |
| Interrupts/diagnostics/status information |
| Diagnostics indication LED |
| Bus fault BF (red) | Yes |
| Run mode RUN (green) | Yes |
| Status indicator digital input (green) | Yes |
| Galvanic isolation |
| between electronic block and PROFIBUS DP | Yes |
| Galvanic isolation digital inputs |
| Galvanic isolation digital inputs | No |
| Galvanic isolation digital outputs |
| Galvanic isolation digital outputs | No |
| between the channels, in groups of | 8 |
| Ambient conditions |
| Operating temperature |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C; 40°C for other mountings |
| Air pressure |
| permissible range, min. | 795 hPa |
| permissible range, max. | 1080 hPa |
| Relative humidity |
| Operation, min. | 15 % |
| Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Degree and class of protection |
| IP20 | Yes |
| Connection method |
| Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Dimensions |
| Width | 160 mm; EB and TB |
| Height | 130 mm; EB and TB |
| Depth | 60 mm; EB and TB |
| Weight |
| Weight, approx. | 650 g; EB and TB |
| Status | Mar 5, 2012 |