| | SIMATIC DP, ELECT. SUBMODULE FOR ET 200ISP, 4 DO, DC 17,4V/40MA |
| |
| Input current |
| from load voltage L+ (without load), max. | 400 mA |
| Power losses |
| Power loss, typ. | 2.8 W |
| Digital outputs |
| Number/binary outputs | 4 |
| Functionality/short-circuit strength | Yes |
| No-load voltage Uao (DC) | 17.4 V |
| Internal resistor Ri | 150 Ω |
| Trend key points E |
| Voltage Ue (DC) | 11 V |
| Current Ie | 40 mA; 80 mA when outputs connected in parallel |
| Output delay with resistive load |
| 0 to "1", max. | 2 ms |
| 1 to "0", max. | 1.5 ms |
| Parallel switching of 2 outputs |
| for increased power | Yes |
| Switching frequency |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 2 Hz |
| Cable length |
| Cable length, shielded, max. | 200 m |
| Cable length unshielded, max. | 200 m |
| Interrupts/diagnostics/status information |
| Alarms |
| Alarms | No |
| Diagnostic alarm | Yes; Parameterizable |
| Diagnostic messages |
| Diagnostic information readable | Yes |
| Wire break | Yes; R > 10 kohms, I < 100 µA |
| Short circuit | Yes; R< 800 ohms (one output), R< 40 ohms (outputs connected in parallel) |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Status indicator digital output (green) | Yes; Per channel |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| between the channels and the load voltage L+ | Yes |
| Permissible potential difference |
| between different circuits | 60 V DC/30 V AC |
| Standards, approvals, certificates |
| CE mark | Yes |
| Use in hazardous areas |
| Type of protection acc. to EN 50020 (CENELEC) | II2 G (1) GD EEx ib[ia] IIC T4 |
| Type of protection acc. to KEMA | 04 ATEX 1249 |
| Dimensions |
| Width | 30 mm |
| Height | 129 mm |
| Depth | 136.5 mm |
| Weight |
| Weight, approx. | 255 g |