| | SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DO 24...230V AC, 15 MM WIDTH 5 PIECES PER PACKAGING UNIT |
| |
| Supply voltage |
| Reverse voltage protection | Yes; when using the same load voltage as on the power module |
| Load voltage L+ |
| Reverse polarity protection | Yes |
| Load voltage L1 |
| Rated value (AC) | 24.23 V; From power module |
| permissible range, lower limit (AC) | 24 V |
| permissible range, upper limit (AC) | 230 V |
| permissible frequency range, lower limit | 47 Hz |
| permissible frequency range, upper limit | 63 Hz |
| Input current |
| from load voltage L+ (without load), max. | 30 mA |
| from load voltage L1 (without load), max. | 15 mA; Per channel |
| from backplane bus 3.3 V DC, max. | 18 mA |
| Power losses |
| Power loss, typ. | 4 W |
| Address area |
| Address space per module |
| with packing | 2 bit |
| without packing | 1 byte |
| Digital outputs |
| Number/binary outputs | 2 |
| Size of motor starter, max. | up to 40 °C size acc. to NEMA: 5; up to 60 °C size acc. to NEMA: 4 |
| Functionality/short-circuit strength | Yes; via fuse in power module |
| Limitation of inductive shutdown voltage to | -55 to -60 V |
| Lamp load, max. | 100 W |
| Zero-crossing switch | Yes; Max. 25 V |
| Controlling a digital input | Yes; possible |
| Output voltage |
| for signal "1", min. | L+ (-1.5 V) |
| Output current |
| for signal "1" rated value | 2 A |
| for signal "1" permissible range for 0 to 60 °C, min. | 0.1 mA |
| for signal "1" permissible range for 0 to 60 °C, max. | 2.2 A |
| for signal "0" residual current, max. | 3 mA |
| Output delay with resistive load |
| 0 to "1", max. | 15 ms |
| 1 to "0", max. | 15 ms |
| Parallel switching of 2 outputs |
| for increased power | No |
| for redundant control of a load | Yes; per module |
| Switching frequency |
| with resistive load, max. | 10 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 1 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 40 °C, max. | 2 A |
| up to 50 °C, max. | 1.5 A |
| up to 60 °C, max. | 1 A |
| Cable length |
| Cable length, shielded, max. | 1000 m |
| Cable length unshielded, max. | 600 m |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) | No |
| Interrupts/diagnostics/status information |
| Substitute values connectable | Yes; 0/1 |
| Diagnostic messages |
| Diagnostic functions | No |
| Diagnostics indication LED |
| Status indicator digital output (green) | Yes |
| Parameter |
| Remark | 3 bytes |
| Behavior on CPU/Master STOP, channel-wise | Substitute a value/keep last value |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| Isolation |
| Isolation checked with | 2500 V DC |
| Dimensions |
| Width | 15 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weight |
| Weight, approx. | 37 g |
| Status | Mar 12, 2012 |