| | SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 16 DO, 120V DC/1A WITH 1 POINT COMMON |
| |
| General information |
| Vendor identification (VendorID) | 0028h |
| Supply voltage |
| 24 V DC | Yes |
| Reverse polarity protection | Yes |
| Mains buffering |
| Mains buffering, min. | 20 ms |
| Power losses |
| Power loss, typ. | 18.9 W |
| Hardware configuration |
| Rack |
| Required terminal block | TB 16L AC |
| Digital outputs |
| Number/binary outputs | 16 |
| Size of motor starter, max. | Size 4 to NEMA (up to 40 °C); size 3 to NEMA (up to 60 °C) |
| Functionality/short-circuit strength | No |
| Lamp load, max. | 50 W |
| Controlling a digital input | Yes |
| Output voltage |
| Rated value (AC) | 120 V |
| for signal "1", min. | Ua - 1,5 V |
| Output current |
| for signal "1" rated value | 1000 mA; Pilot mode |
| for signal "1" permissible range, min. | 100 mA |
| for signal "1" permissible range, max. | 1 A |
| for signal "0" residual current, max. | 2.6 mA |
| Output delay with resistive load |
| 0 to "1", max. | 20 ms |
| 1 to "0", max. | 20 ms |
| Parallel switching of 2 outputs |
| for increased power | No |
| for redundant control of a load | Yes |
| Switching frequency |
| with resistive load, max. | 10 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 1 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 60 °C, max. | 1 A; per output |
| all other mounting positions |
| up to 40 °C, max. | 0.4 A |
| Cable length |
| Cable length, shielded, max. | 1000 m |
| Cable length unshielded, max. | 600 m |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 1.5 Mbit/s; 9.6 / 19.2 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 3 / 6 Mbit/s |
| SYNC capability | Yes |
| Direct data exchange (slave-to-slave communication) | Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
| Communication functions |
| Bus protocol/transmission protocol | PROFIBUS DP |
| Interrupts/diagnostics/status information |
| Alarms |
| Alarms | No |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostics indication LED |
| Bus fault BF (red) | Yes |
| Status indicator digital output (green) | Yes |
| Status indicator digital input (green) | Yes |
| Monitoring 24 V voltage supply ON (green) | Yes |
| Galvanic isolation |
| between PROFIBUS DP and all other circuit components | Yes |
| Galvanic isolation digital outputs |
| between the channels | Yes |
| between the channels and PROFIBUS DP | Yes |
| Isolation |
| Isolation checked with | 1500 V AC |
| Ambient conditions |
| Operating temperature |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C; 40°C for other mountings |
| Air pressure |
| permissible range, min. | 795 hPa |
| permissible range, max. | 1080 hPa |
| Relative humidity |
| Operation, min. | 5 % |
| Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Degree and class of protection |
| IP20 | Yes |
| Connection method |
| Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
| Dimensions |
| Width | 191 mm |
| Height | 61 mm |
| Depth | 85.5 mm |
| Weight |
| Weight, approx. | 294 g |
| Status | Mar 12, 2012 |