| | SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, DIGITAL, 16 DO 0,5A, 24V DC, EXPANDABLE WITH MAX. 16 CHANNELS W. TERM. BLOCK TB 16SC OF SMART CONNECT |
| |
| General information |
| Vendor identification (VendorID) | 8028h |
| Supply voltage |
| Mains buffering |
| Mains buffering, min. | 20 ms |
| Load voltage L+ |
| Rated value (DC) | 24 V |
| Input current |
| from load voltage L+ (without load), max. | 50 mA |
| from supply voltage L+, max. | 180 mA |
| Power losses |
| Power loss, typ. | 4 W |
| Hardware configuration |
| Rack |
| Required terminal block | TB 16L (expansion: digital and analog with SIMATIC SC) |
| Digital outputs |
| Number/binary outputs | 16 |
| Functionality/short-circuit strength | Yes; Electronic |
| Response threshold, typ. | 0.7 A |
| Limitation of inductive shutdown voltage to | Typ. (L1+ or L2+ / L3+) -55 V |
| Lamp load, max. | 5 W |
| Controlling a digital input | Yes |
| Load resistance range |
| lower limit | 41 Ω |
| upper limit | 28000 Ω |
| Output voltage |
| Rated value (DC) | 24 V |
| for signal "1", min. | Ua - 3 V |
| Output current |
| for signal "1" rated value | 500 mA |
| for signal "1" permissible range for 0 to 40 °C, min. | 1 mA |
| for signal "1" permissible range for 0 to 40 °C, max. | 500 mA |
| for signal "1" permissible range for 0 to 60 °C, max. | 0.5 A |
| for signal "0" residual current, max. | 1 mA |
| Output delay with resistive load |
| 0 to "1", max. | 50 ms |
| 1 to "0", max. | 200 ms |
| Parallel switching of 2 outputs |
| for increased power | No |
| for redundant control of a load | Yes; only outputs of the same group |
| Switching frequency |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 8 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 60 °C, max. | 4 A |
| Total current of the outputs (per module) |
| horizontal installation |
| up to 40 °C, max. | 3 A |
| up to 60 °C, max. | 2 A |
| all other mounting positions |
| up to 40 °C, max. | 2 A |
| Relay outputs |
| Rated input voltage of relay coil L+ (DC) | 24 V |
| Reverse polarity protection | Yes |
| Cable length |
| Cable length, shielded, max. | 1000 m |
| Cable length unshielded, max. | 600 m |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 1.5 Mbit/s |
| SYNC capability | Yes |
| FREECE capability | Yes; for SC inputs |
| Communication functions |
| Bus protocol/transmission protocol | PROFIBUS DP |
| Interrupts/diagnostics/status information |
| Alarms |
| Alarms | No |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostics indication LED |
| Bus fault BF (red) | Yes |
| Group error SF (red) | Yes |
| Status indicator digital output (green) | Yes |
| Monitoring 24 V voltage supply ON (green) | Yes |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| between the channels | No |
| between the channels and PROFIBUS DP | Yes |
| Isolation |
| Isolation checked with | 500 V DC |
| Dimensions |
| Width | 145 mm |
| Height | 60 mm |
| Depth | 60.5 mm |
| Weight |
| Weight, approx. | 130 g |
| Status | Mar 5, 2012 |