| | SIMATIC DP, DIGITAL ELECTRONIC SUBMODULE FOR ET200B W=235MM, 16DO, 120/230V AC,0.5A |
| |
| Input current |
| from supply voltage L1, max. | 150 mA |
| Power losses |
| Power loss, max. | 11 W |
| Hardware configuration |
| Rack |
| Required terminal block | TB6/AC |
| Digital outputs |
| Number/binary outputs | 16 |
| Size of motor starter, max. | Size 3 to NEMA |
| Functionality/short-circuit strength | No |
| Lamp load, max. | 25 W |
| Controlling a digital input | Yes |
| Output voltage |
| Rated value (AC) | 120/230 V AC |
| Output current |
| for signal "1" permissible range for 0 to 60 °C, min. | 0.5 A; in groups of 4 |
| for signal "0" residual current, max. | 1.3 mA |
| Parallel switching of 2 outputs |
| for logic links | Yes |
| for increased power | No |
| for redundant control of a load | Yes |
| Switching frequency |
| with resistive load, max. | 10 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 1 Hz |
| Cable length |
| Cable length unshielded, max. | 600 m |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 12 Mbit/s |
| Communication functions |
| Bus protocol/transmission protocol | PROFIBUS DP |
| Interrupts/diagnostics/status information |
| Diagnostics indication LED |
| Bus fault BF (red) | Yes |
| Run mode RUN (green) | Yes |
| Status indicator digital output (green) | Yes |
| Galvanic isolation |
| between electronic block and PROFIBUS DP | Yes; 500 V DC to the logic, 1500 V AC to connecting terminals |
| Galvanic isolation digital outputs |
| Galvanic isolation digital outputs | Yes; Optocoupler |
| between the channels, in groups of | 4 |
| Ambient conditions |
| Operating temperature |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C; 40°C for other mountings |
| Air pressure |
| permissible range, min. | 795 hPa |
| permissible range, max. | 1080 hPa |
| Relative humidity |
| Operation, min. | 15 % |
| Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Degree and class of protection |
| IP20 | Yes |
| Connection method |
| Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Dimensions |
| Width | 235 mm; EB and TB |
| Height | 130 mm; EB and TB |
| Depth | 60 mm; EB and TB |
| Weight |
| Weight, approx. | 805 g; EB and TB |
| Status | Mar 5, 2012 |