| | SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8 RO 24V - 60V DC, DEGR. OF PROTECT. IP20,STANDARD |
| |
| Supply voltage |
| 24 V DC | Yes; L3+; value at t < 0.5 s: 35 V |
| permissible range, lower limit (DC) | 18.5 V |
| permissible range, upper limit (DC) | 30.2 V |
| Input current |
| Current consumption, max. | 130 mA; from L3+; logic |
| I²t | 0.05 A²·s; with starting current inrush |
| Power losses |
| Power loss, typ. | 2 W |
| Hardware configuration |
| Rack |
| Required terminal block | TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC |
| Digital outputs |
| Number/binary outputs | 8; Relay |
| Functionality/short-circuit strength | No |
| Controlling a digital input | Yes |
| Output voltage |
| Rated value (DC) | 24 V; 24 to 60 V DC |
| Switching frequency |
| with resistive load, max. | 10 Hz |
| with inductive load, max. | 2 Hz |
| Relay outputs |
| Switching capacity of contacts |
| with inductive load, max. | 0.5 A; at 30 V DC |
| Switching frequency/contacts/at ohmic load/maximum | 2 A; at 24 V DC; max. 1.5 A at 48 V DC; max. 1 A at 60 V DC |
| Thermal continuous current, max. | 5 A |
| Cable length |
| Cable length unshielded, max. | 100 m |
| Interfaces |
| PROFIBUS DP |
| Transmission rate, max. | 12 Mbit/s |
| SYNC capability | Yes |
| Communication functions |
| Bus protocol/transmission protocol | PROFIBUS DP |
| Interrupts/diagnostics/status information |
| Diagnostics indication LED |
| Bus fault BF (red) | Yes |
| Run mode RUN (green) | Yes |
| Status indicator digital output (green) | Yes |
| Galvanic isolation |
| between electronic block and PROFIBUS DP | Yes |
| Galvanic isolation digital outputs |
| Galvanic isolation digital outputs | Yes |
| between the channels, in groups of | 1 |
| Ambient conditions |
| Operating temperature |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C; 40°C for other mountings |
| Air pressure |
| permissible range, min. | 795 hPa |
| permissible range, max. | 1080 hPa |
| Relative humidity |
| Operation, min. | 15 % |
| Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Degree and class of protection |
| IP20 | Yes |
| Connection method |
| Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Dimensions |
| Width | 160 mm; EB and TB |
| Height | 130 mm; EB and TB |
| Depth | 60 mm; EB and TB |
| Weight |
| Weight, approx. | 650 g; EB and TB |
| Status | Mar 5, 2012 |